VOLTAGE, CURRENT AND FREQENCY RANGES
SPECIFIED AC OUTPUT VOLTAGE OF AN LA SERIES GRID-INTERACTIVE SYSTEM
Single Phase
Series Stacked
Three Phase Stacked
RECOMMENDED FX DC VOLTAGE RANGE
Note: The last two digits in the model number designate the nominal DC voltage.
Example: GVFX3648LA =48V DC Voltage.
24V Systems
48V Systems
MAXIMUM DC INPUT CURRENT
Note: This is the maximum DC current the FX will draw from the battery when starting very large AC loads.
It is not used for sizing the DC disconnect or selecting DC cable gauge. It is used to select the minimum
reasonable battery capacity.
24V FXs
48V FXs
RATED DC INPUT CURRENT
Note:
This is the maximum continuous DC current that the FX will draw from the batteries when inverting.
GTFX2524LA
GTFX3048LA
GVFX3524LA
GVFX3648LA
AC INPUT OPERATING VOLTAGE RANGE
Note: If the AC input source is out of the range noted below, the FX will not connect or stay connected.
All LA Series Inverter/Chargers
AC INPUT FREQUENCY RANGE
Note: If the AC input source is out of the range noted below, the FX will not connect or stay connected.
All LA Series Inverter/Chargers
76
127 VAC at 60 Hz
127 VAC at 60 Hz per AC output leg / 254 VAC at 60 Hz between the AC output legs
127 VAC at 60 Hz per AC output leg (limit three) / 220 VAC at 60 Hz between AC output legs
22 – 32 VDC (VDC = volts DC)
44 – 64 VDC
300 ADC per FX (ADC = amps DC)
150 ADC per FX
125 ADC (ADC = Amps DC)
75 ADC
175 ADC
90 ADC
100 – 140 VAC (VAC = volts AC)
58 - 62 Hz