Mitsubishi Electric CMB-P-V-F Manual De Instalación página 2

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 19
2
2.1
[Fig. 2.1.1]
[Fig. 2.2.2]
B
B
118
362
53
Model name
A
CMB-P104V-F
648
CMB-P105V-F
648
CMB-P106V-F
648
CMB-P108V-F
648
CMB-P1010V-F
648
CMB-P1013V-F
1098
CMB-P1016V-F
1098
Item
Total piping length
Longest piping length
Between outdoor and BC
controllers
Between indoor and BC controllers
Above outdoor
Between indoor
and outdoor
Below outdoor
Between indoor and BC controllers
Between indoor and indoor
3
[Fig. 3.2.1]
B
D
1
2
A
A
77
A
77
A On the side of outdoor unit piping
B On the side of indoor unit piping
Piping portion
Allowable value
A+B+a+b
Below 220
+c+d+e
Below 100
A+e
(Below 90)*1
Below 70
A
(Below 60)*1
e
Below 30
H
Below 50
H1
Below 40
Below 15
h1
(Below 10)*2
Below 15
h2
(Below 10)*2
A
C
2
[Fig. 2.2.1]
200
<A>
A
450
C
B
D
INDOOR UNIT SIDE
200
A
A Inspection hole
B On the side of outdoor unit piping
C Control box
D On the side of indoor unit piping
*1 Dimensions with which pipe connection can be handled at site
[Fig. 2.3.1]
(Unit: m)
A Outdoor unit
C Indoor unit
E Less than H=50 m (when the outdoor unit is higher than the indoor unit)
F Less than H1=40 m (when the outdoor unit is lower than the indoor unit)
G Branch pipe (for Y Series) CMY-Y102S-F
H Combined pipe (CMY-R160-H: optional)
I Less than 70 (60 m)
K Up to three units for 1 branch hole
Total capacity: less than 80 (but same in cooling/heating mode)
L Less than h1=15 m (10 m or less for 125, 140 unit type)
M Less than h2=15 m
Notes:
*1 In the table, if the total capacity of indoor units exceeds 130 % of outdoor
units, it will be the values inside parentheses.
*2 10 m or less, with indoor units with model numbers of 125, 140.
3.2
D
C
B
E
2.2
<B>
B
Model name
CMB-P104V-F
CMB-P105V-F
CMB-P106V-F
CMB-P108V-F
CMB-P1010V-F
CMB-P1013V-F
CMB-P1016V-F
2.3
A
I
A
B
J
H
a
G
C
b
B
c
d
C
C
C
D
K
B BC controller
D More than 81
J Less than 30 m
1 Hanging method
2 Installing-on-the-floor method
A: Min.30
A Hanging bolt ø10 (field supply)
B Nut (field supply)
C Washer (field supply)
D Double nuts (field supply)
E Anchor bolt M10 (field supply)
<A> Top view
<B> Front view
A
648
648
648
648
648
1098
1098
e
C