Installation
Neutral assembly (optional)
Neutral assembly (EOHXSN78), optional
Install the neutral link on the bottom plate of the safety switch
to the existing threaded holes according to the picture. See
chapter Cabling.
EOHXSN78:
Wire range: (4) #2 - 600 kcmil / 4 x 35 -300 mm
Torque: wire tightening for Cu and Al cables 500 lbs.in / 55.7 Nm
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
2
Failure to follow these instructions will result in death or serious injury.
Instruction Bulletin EOHU367, EOHU368, 1SCC340039M1401 / A | Installation 1/13