5.1 Remote display terminal (UUKDI00000)

The LCD terminal is an option and can only be used if the auxiliary card is
fi tted, alreay built-in on models UU**R*AS01.
The terminal displays humidifi er status and can be used to customise
operation by setting the parameters.
CONNECTION:
Key:
1 6-wire telephone cable P/N S90CONN000 or equiv., max. length 2 m (6,6
ft)
(1)
;
2 remote display terminal.
3 auxiliary card
(1)
For lengths exceeding 2 m (6,6 ft), use shielded cable with the shield
connected to the PE both at the terminal and controller end.
Remote connection of the terminal up to 200 m
1
2
SC
A
B
C
J14
J15
1 2 3 1 2 3
3
4
2
SC
A
B
C
J14
J15
1 2 3 1 2 3
3
Key:
1 telephone cable (up to 0.8 m distance);
2 CAREL TCONN6J000 board;
3 pin strip J14 and J15 in position 1-2 (power supply available on the
telephone connectors A, B and C and screw SC);
4 WG20-22 shielded cable with 3 twisted pairs to move the display
terminal up to 200 m away. Connection to the TCONN6J00 board:
SC terminal
function
0
EARTH (shield)
1
+VRL
2
GND
3
RX/TX-
5 remote display terminal
6 auxiliary card

5.2 Meaning of the symbols

Power supply (Green LED)
Humidifi er operating (yellow LED)
Steady: humidity production in progress
Flashing: transitory status, atomisation temporarily paused
Direct version for room applic. +0300062IE - rel. 1.3 - 15.07.2019
5. LCD TERMINAL OPTIONAL
esc
Fig. 5.a
esc
Fig. 5.b
humiSonic
6
esc
5
Fig. 5.a
SC terminal
function
4
RX/TX+
5
GND
6
+VRL
Alarm (red LED)
On activation of an alarm: LED fl ashing and buzzer active. When an
alarm is active, pressing ESC mutes the buzzer and the LED comes
on steady, pressing ESC again resets the alarms (see chap. "Alarms")
Time in seconds
Hour counter
Humidity production as a percentage of rated capacity
Maintenance request (active alarm)
On steady: humidifi er fan operating.
Flashing: fan on during deactivation phase
3 digits, after 999 the display shows to indicated the 1000s (the
three digits are displayed with a dot at the top between the fi rst
and second digit).
Humidity production in progress
Tank fi lling
Water in the tank
Water draining from the tank (showned even if unit is in stand-by
mode, because drain valve is normally open)

5.3 Keypad

Button
Function
return to the previous display
UP
from the main screen: display the humidifi cation values, see
the following paragraph
from the list of parameters: scroll the parameters and set the
values
DOWN from the main screen: display the humidifi cation values
from the list of parameters: scroll the parameters and set the
values
ENTER
for 2 seconds: access the list of parameters
inside the list of parameters: select and confi rm (like "Enter" on
(PRG)
a computer keyboard)
drain
manual drain: press UP and DOWN together

5.4 Main display

The humidifi er display normally shows control signal status. For ON/
OFF or proportional input signal (A0=0, A0=1, A0=3 and Th probe
disconnected):
display input signal;
tank hour counter (h);
maximum atomized water production control (parameter P0) (*);
control hysteresis (parameter P1) (*);
humidifi er status (Enb = enabled): pressing ENTER disables the
humidifi er and dIS is shown on the main screen.
For humidity probe input signal (A0=2, A0=3 and Th probe connected):
display humidity probe reading;
display temperature (Th only);
tank hour counter (h);
maximum atomized water production control (parameter P0) (*);
proportional band (parameter bP)(*);
humidity Setpoint (parameter SP)(*);
humidifi er status (Enb = enabled): pressing ENTER disables the
humidifi er and dIS is shown on the main screen.
If enabling probe TH as a humidity limit probe (bH=1) in contorl modes
A0=0, A0=1, A0=3, the following parameters will be added to the main
screen:
humidity limit set point (parameter SL) (*);
limit proportional band (parameter bL) (*)
To return to the main display press ESC. Parameter C0 (see chap.
"Confi guration parameters") can be used to change the value shown on
the main display (default: display input signal).
Disabling options:
from remote (ON-OFF contact open), the display shows "C - -"
alternating with the main screen;
on the display, by pressing ENTER on Enb, the display will then show
dIS (to enable it again, press ENTER); for a master/slave network, this
only disables the individual humidifi er in question;