LOCATION OF GAS RATING PLATE
IMPORTANT
NEVER REUSE OLD CONNECTORS WHEN INSTALLING THIS
RANGE.
To reduce the likelihood of gas leaks, apply teflon tape or a
thread compound approved for use with LP or Natural gases
to all threaded connections.
Apply a non-corrosive leak detection fluid to all joints and
fittings in the gas connection between the supply line shut-off
valve and the cooktop inlet.
Check for leaks!
Bubbles appearing around fittings and connections will
indicate a leak. If a leak appears, turn off supply line gas
shut-off valve, tighten connections, turn on the supply line gas
shutoff valve, and retest for leaks. Never test for gas leaks
with an open flame.
NEVER TIGHTEN TO MORE THAN 35 ft lbs OF TORQUE
CAUTION
Do not attempt to attach the flexible connector directly to an
external pipe thread.
Connection requires flare union adapters.
For Massachusetts Installations:
1. Shut-off valve must be a "T" handle gas valve.
2. Flexible gas connector must not be longer than 36 inch.
3. Not approved for installation in a bedroom or a bathroom
unless unit is direct vent.
5 - Gas Requirement

Pressure Testing

The appliance must be isolated from the gas supply piping
system by closing its individual manual shut-off valve during
any pressure testing of the gas supply piping system at test
pressures equal to or less than 1/2 PSIG (3.5 kPa).
This appliance, as well as its individual shut-off valve, must be
disconnected from the gas supply piping system during any
pressure testing of the system at test pressures in excess of 1/2
PSIG (3.5 kPa).
When checking appliance regulator function, make certain
pressure of natural gas supply is between 6 and 14 inches of
water column or, if converted for LP gas, between 11 and 14
inches.
THE PRESSURE TESTING SHOULD BE PERFORMED BY
MEANS OF THE INJECTOR THREAD ZONE
EXPLODED VIEW OF BURNER

Pressure Test Method

• Remove grate and burner cap (1).
• Remove aluminum gas spreader (2).
• Temporarily remove the injectors (A).
• Connect the pressure Test instrument into injector holder
thread zone (M6x0,75).
• Check if the cooktop has the correct pressure.
• Fix the injector removed for testing and replace the parts in
the right position.
EN
1
2
A
13