N°REG.
Register
47
VIERNES T3
48
SABADO T1
49
SABADO T2
50
SABADO T3
51
DOMINGO T1
52
DOMINGO T2
53
DOMINGO T3
54
TIEMPO T1
55
TIEMPO T2
56
TIEMPO T3
57
CONSIGNA T1
58
CONSIGNA T2
59
CONSIGNA T3
60
FECHA INICIO
61
HORA INICIO
62
FECHA FIN
63
HORA FIN
64
CONSIGNA VAC
65
VERSION
66
BAUDRATE
67
PARIDAD
Input registers (Read-only)
Register
Min.
0
Pote
1
In1
2
In2
3
Interno
4
Rpm
Discrete inputs (Read-only)
Register
Min.
0
InD
Output coils (sólo lectura)
Register
Min.
0
Output
Min.
Max.
Description
0x0000
0x063b
Hour/Minute
0x0000
0x063b
Hour/Minute
0x0000
0x063b
Hour/Minute
0x0000
0x063b
Hour/Minute
0x0000
0x063b
Hour/Minute
0x0000
0x063b
Hour/Minute
0x0000
0x063b
Hour/Minute
0
480
0
480
0
480
0
100
0
100
0
100
0
0xfe7f
Day/Month/Year
0x0000
0x063b
Hour/Minute
0
0xfe7f
Day/Month/Year
0x0000
0x063b
Hour/Minute
0
100
0
250
0
3
0
2
Max.
Description
Potentiometer RV1
0
255
0
255
Analog input 1
0
255
Analog input 2
Internal pressure
0
1250
0
6000
Motor speed
Max.
Description
0
1
Digital input
Max.
Description
0
1
Default
0x0480
0x0200
0x0300
0x0480
0x0200
0x0300
0x0480
1
60
1
60
1
60
1
80
1
60
1
100
0x088E
0
0x088E
0
1
20
1
0=19200
1=9600
1
2=4800
3=2400
0=No
1=Even
1
2=Odd
Default
Comments
PCB
sensor
Default
Comments
Default
Comments
Relay
65
Comments
Starting period 3 Friday
Starting period 1 Saturday
Starting period 2 Saturday
Starting period 3 Saturday
Starting period 1 Sunday
Starting period 2 Sunday
Starting period 3 Sunday
Time in minutes for period
1
Time in minutes for period
2
Time in minutes for period
3
Percentage about set point
Percentage about set point
Percentage about set point
Starting date holiday
period
Starting hour/minute
holiday period
Ending date holiday period
Ending hour/minute
holiday period
Holiday period set point
Read-only
Transmission speed
Parity MODBUS network
Comments
Potentiometer RV1
Entrada Analógica 2
Entrada Analógica 2
Internal pressure sensor
Speed motor
(if rpm<100, rpm=0)
Comments
Digital input
Comments
Relay