AKO -522014 Manual Del Usuario página 16

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Button assembly
The button should be installed inside the coldroom, in a visible place and no higher than 125 cm from
the floor.
- Remove the button's cover (Fig. 4).
- Drill the hole for the glands needed for the cable entry following the pre-stamped centres on the bottom or top of
the base.
- Drill 3 holes on the wall following the fixing holes. (Fig. 5).
- Fasten the gland onto the base.
- Insert the 3 screws+plugs through the base, into the 3 holes on the wall and tighten.
- Insert the cables into the gland and connect them according to the wiring diagram.
- Insert the cover and gently press it until you hear a "click".
FIG. 4
Press gently
Fixing holes suitable for universal
built-in housing
Detector assembly
The detector should be installed in an area where the highest
amount of gas may concentrate, near places where gas leaks
could start and accessible for maintenance work. It is also
advisable to place it away from transit areas or areas where it could be
accidentally knocked.
Different types of gas can have different densities, and this means that
leaks could concentrate in the lowest part of the room or near the roof.
Take this into account when deciding on the height of the detector.
It is advisable to install the freon detectors around 20 cm from the
ground, with an free distance around them of some 50 cm.
- Remove the detector's cover (Fig. 6).
- Drill the hole for the glands needed for the cable entry following the
pre-stamped centres on the bottom or top of the base.
- Drill 3 holes in the wall following the fixing holes. (Fig. 7).
- Fasten the gland onto the base.
- Insert the 3 screws+plugs through the base, into the 3 holes on the
wall and tighten.
- Insert the cables into the gland and connect them according to the
wiring diagram.
- Adjust the
alarm/pre-alarm delays using the delay switch
(See page 14).
- Insert the cover and gently press it until you hear a "click".
Max. Ø 3.7
FIG. 5
35
125,5
171
FIG. 4
FIG. 5
16
Fixing hole detail
Press gently
Fixing holes suitable for universal
built-in housing
Delay switch
Max. Ø 3.7
Fixing
holes
35
125,5
168

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Ako-522024Ako-522104Ako-52211Ako-52212Ako-52062

Tabla de contenido