If the pre-alarm does not activate, check that it has not been cancelled in the alarm station.
- If the pre-alarm or alarm do not activate, try it again releasing gas for a longer time.
-An excessive exposure might reduce the delay between the activation of the pre-alarm and the alarm, and
lengthen the waiting time for their deactivation.
-Remember to press the reset button to delete the alarm log (green button) after checking.
When you have finished the check, remember to turn the delay switch to its initial configuration again,
disconnecting the power supply before using it.
7.- Technical data
AKO-522104
Power supply ........................................................................................................................90-260 V~ 50/60 Hz
Maximum input power ................................................................................................................................20 VA
Accumulators ..................................................................................................................................Ni-MH 1.6 Ah
Lighting + alarm duration ..............................................................................................................> 10 Hours (*)
No. of inputs.......................................................................................................................................................4
Compatibility of inputs.............................................................................................................AKO-52062 button
Gas alarm/prealarm relay ..........................................................................................SPST 230 Vac, 16 A, cos j =1
Trapped person alarm relay .......................................................................................SPDT 230 Vac, 16 A, cos j =1
Working ambient temperature ..........................................................................................................0 ºC to 50 ºC
Storage ambient temperature .........................................................................................................-30 ºC a 70 ºC
Protection degree .........................................................................................................................................IP 65
Installation category .....................................................................................................................II s/EN 61010-1
Pollution degree ...........................................................................................................................II s/EN 61010-1
Double isolation between power supply, secondary circuit and relay output.
Sound power..........................................................................................................................90 dB(A) at 1 metre
AKO-52211/52212
Power supply..................................................................................................................................15 Vdc ±3 Vdc
Consumption Typical ...............................................................................................................................75 mA
Maximum ........................................................................................................................100 mA
Working ambient temperature .......................................................................................................-20 ºC to 50 ºC
Storage ambient temperature .........................................................................................................-20 ºC a 60 ºC
Range of maximum allowed humidity .............................................................5 - 85% RH (without condensation)
Protection degree .........................................................................................................................................IP 40
Life.........................................................................................Depending on temperature and humidity conditions
EMC Standard ......................................................................................................................................EN 61000
AKO-52062
Power supply..................................................................................................................................15 Vdc ±3 Vdc
Working ambient temperature .......................................................................................................-50 ºC to 50 ºC
Storage ambient temperature .........................................................................................................-50 ºC a 70 ºC
Protection degree ..........................................................................................................................................Ip65
*Duration with 4 push-buttons connected to an ambient temperature of 5 to 30 ºC.
Only S1 and S2: .......................AKO-52062 button or AKO-52211/52212 gas detector