Parameter Table - LOVATO ELECTRIC DME D305T2MID Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

– The following table lists the available menus:
CODE
MENU
GENERAL
P01
P02
UTILITY
P03
PASSWORD
P04
INTEGRATION
P05
HOUR COUNTER
P08
LIMIT THRESHOLDS (LIMn)
P09
ALARMS (ALAn)
P11
ENERGY PULSES (PULn)
P13
INPUTS
P14
OUTPUTS
– Press
to access the selected menu.
– At this point the sub-menu (if applicable) and sequential parameter number can be selected, again using the buttons as follows:
• s and t simultaneously: back
• t decrease
• s increase
next
– Once the desired parameter number is set,
– Pressing s or t changes the parameter within the permitted range.
– Pressing t and
simultaneously sets the minimum possible value, while pressing s and
– Pressing s and t simultaneously restores the factory default value.
– After selecting the desired value, pressing
– Press s and t simultaneously several times to exit and save the parameters. The device will reboot.
– If no buttons are pressed for two minutes, the setup menu is abandoned automatically and the system returns to the standard display without saving the parameters.
– Remember that, solely for the data that can be edited using the buttons, a backup copy can be made in the DME D305T2MID's EEPROM. If required, this data can be restored to the working memory. The backup
and data restore commands are in the commands menu.

PARAMETER TABLE

– All available programming parameters are indicated in the following table. For each parameter the range of possible settings and factory default are shown, in addition to an explanation of the parameter's function.
The description of the parameter visible on the display may in some cases vary from that indicated in the table due to the limited number of characters available. The parameter code is a valid reference in any case.
M01 - GENERAL
P01.01
CT primary
P01.02
CT secondary
P01.03
Nominal voltage
P01.04
Nominal power
P01.05
Connection type
P01.01 – Rated current of CT primary winding.
P01.02 – Current of CT secondary winding.
P01.03 – Rated voltage of system.
P01.04 – Rated power of system.
P01.05 – Set in accordance with the connection scheme adopted. See Wiring Diagram at the end of the manual.
Setup: selecting the parameter number
switches to parameter value edit mode, with the parameter shown in the alphanumeric display.
stores the parameter and returns to the previous level, i.e. parameter selection.
DESCRIPTION
Specifications of the system
Language, brightness, display, etc.
Enablement of protected access
Readings integration times
Enablement of hour counter
Measurement thresholds
Alarm messages
Energy pulse configuration
Programmable input
Programmable outputs
sets the maximum.
UoM
Default
Range
A
5
1-10000
A
5
V
AUT
AUT / 220-415
kW
AUT
AUT / 1-10000
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
G
B
1-5
L1-N
9