Page
Code
Measurement page displayed when
HoME
P11
turned on and after 120 seconds of
disuse
Enable
requested power and partial active and
rESET
P17
reactive energy reset (the latter only sent
via serial port)
Return to the initial measurement page
End
P18
Pages specific to the S1 version
Page
Code
AddrESS
P14
bAUd
P15
PArITY
P16
STOP bit
P16–2
Pages specific to the O1 version
Page
Code
Pulse time (ON time, milliseconds)
PULSE
P12
PulrAtE
P12–2
Pulse weight. Multiples of 100 impulses/kWh.
Pages specific to the M1 version
Page
Code
Pr I Add
P13
bAUd
P15
8021422 | EM330
Description
energy
tariff,
maximum
Description
Modbus address
Baud rate (kbps)
Parity
Only if no parity. Stop bit.
Description
Description
M-Bus primary address
Baud rate (kbps)
Values
For full display mode (Mode = Full): 0–19
For reduced display mode (Mode = Easy): 0–3, 6, 7,
10/11, 18
To learn the page code see
16)" on page 7.
No: cancel reset/ Yes: enable reset
–
1–247
9.6/ 19.2/ 38.4/ 57.6/ 115.2
Even/ No
1/ 2
30/ 100
For 30 ms: 100–2000
For 100 ms: 100–500
1–250
0.3/ 2.4/ 9.6
©2014 | CARLO GAVAZZI Controls SpA| 10
"Measurement (Fig.
Values
Values
Values