• A window will then be displayed for the setting of the energy value corresponding
to each impulse
• Press the "up" ( ) or "down" ( ) keys to select the value of the flashing
digit and pK to go to the next digit
• By default, the weight of the impulse (set on calibration and on each modification
of the TA/TV) is equivalent to:
- 1 impulse every "20 x value primary TA" Wh/varh,
for primary TV up to 230 V
- 1 impulse every "40 x value primary TA" Wh/varh,
for primary TV from 230 to 580 V
- for the primary TV over 580 V, the impulse output is inactive
These are the minimum values that can be set for the impulse weight
The duration of the impulse is always constant and equivalent to 100ms
DISPLAYING THE MEASUREMENT PAGES
■ When the instrument is switched on (or after the programming stage), the first
page (relay status) is displayed after approximately 3 seconds with the display
completely on
■ When the "up" key ( ) is pressed from the first page, all the other measurement
pages are displayed in sequence. Press the "up" key ( ) from the last page to
return to the main page.
Note: in the event of incorrect entry (current polarity inverted or no
correspondence between phase voltage and current), the phases involved
are highlighted and the number for the group of symbols at the centre
of the display is cancelled.
➧
➧
pK
k Wh
VARh
- 39 -
User Manual ADR-out Network Analyser
k Wh
VARh
T