Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

SPECIFICATIONS
1. Electrical data
(All accuracies stated at 23°C ± 1°C)
Nominal current In
2000 AC
RMS
Measuring range
200 / 2000A
Overload capacity
2200A (60s)
Output sensitivity
10 / 1mV/A
Overall DC
0 - 200A
±1% of rdg ±0.5A
accuracy
0 – 1500A
±1% of rdg ±0.5A
1500 – 2000A
±5% of rdg
Resolution
±100mA/±500mA
Typical output noise level
600µV / 10µV
Gain variation
±0.15% of reading/°C
DC to 20kHz (-1dB)
Frequency range
I
x f ≤ 400,000
RMS
di/dt response
20A/µs
Response time
5µs
Working voltage
300V AC
2. General data
Operating temperature
0°C to +50°C
Storage temperature with Battery
-20°C to +85°C
removed
Power supply
9 V Alkaline battery
PP3, MN 1604 or
IEC6LR61
Battery life
50 hours typical
> 100kΩ and ≤ 100pF
Load impedance (minimum)
Conductor size
32 mm diameter
Weight
320 g.
1.5 m long coax with 4mm
Output cable and connectors
safety plugs
(CP2005_4mm)
2 m long coax terminated
with a safety BNC
connector 50 Ohms
(CP 2005)
or DC
1
3
4
7
9
or DC
RMS
FIG 1
2
1.
Jaws
2.
Conventional
4
5
current direction
3.
Tactile Barrier
6
4.
Battery cover
5.
Battery cover
screw
8
6.
Jaw trigger
7.
ON/OFF switch
8.
Auto-zero button
9.
LED

SAFETY STANDARDS

EN 61010-1:2010
EN 61010-2-032:2012
300V Cat III, Pollution Degree 2
EMC Standards
EN 61326-2-2:2006
ROHS and WEEE compliant
This product is designed to be safe under the following
conditions:
- Indoor use
- Altitude up to 2000m
- Temperature 0°C to +50°C
- maximum relative humidity 80% for temperatures up to
31°C decreasing linearly to 40% relative humidity at
50°C.
Use of the probe on uninsulated conductors is limited to
300V AC
or DC and frequencies below 1kHz.
RMS
Safety in its use is the responsibility of the operator who must
be a suitably qualified or authorised person. Ensure that your
fingers are behind the protective barrier see FIG 1 when
using the probe.
Always inspect the probe and lead for
damage before use.
To avoid electric shock, keep the probe clean and free of
surface contamination.
Use Isopropyl alcohol to clean the probe.
WARRANTY
Your GMC-I PROSyS current probe is guaranteed for one
year from the date of purchase against defective material or
workmanship. If the probe fails during the warranty period,
we shall at our discretion, repair or replace it with a new or
reconditioned unit provided we are satisfied that the failure is
due to defective material or workmanship. To make a claim
under warranty, the probe should be returned to us, postage
prepaid, with a description of the defect. The use of a battery,
other than that specified invalidates this warranty.
Goods alleged by the buyer to be defective shall not form the
subject of any claim for injury, loss, damage, or any expense
howsoever incurred, whether arising directly or indirectly from
such alleged defects other than death or personal injury
resulting from the seller's negligence.
No condition is made or to be implied, nor is any warranty
given or to be implied as to the life or wear of goods supplied
or that they will be suitable for any particular purpose or for
use under specific conditions, notwithstanding that such
purpose or conditions may be made known to the seller.

Publicidad

Tabla de contenido
loading

Tabla de contenido