Troubleshooting - Allmatic XTILUS Importantes Instrucciones De Seguridad Para La Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

TROUBLESHOOTING

PROBLEM
By giving a command with the remote control or
with the key selector, the gate doesn't open or the
motor doesn't start.
By giving a command with the remote control,
the gate does not open, but it works with the key
selector.
The gate starts, but stops immediately
One wing opens and the other closes
TYPICAL CONNECTION AND CABLE SECTION
230V
4 x 0,75 mm
4 x 0,75 mm
3 x 1,5 mm
230V power supply
GUARANTEE
In compliance with legislation, the manufacturer's guarantee is valid from the date stamped on the product and is restricted to the repair or free replacement of the
parts accepted by the manufacturer as being defective due to poor quality materials or manufacturing defects. The guarantee does not cover damage or defects
caused by external agents, faulty maintenance, overloading, natural wear and tear, choice of incorrect product, assembly errors, or any other cause not imputable to
the manufacturer. Products that have been misused will not be guaranteed or repaired. Printed specifications are only indicative. The manufacturer does not accept any
responsibility for range reductions or malfunctions caused by environmental interference. The manufacturer's responsibility for damage caused to persons resulting from
accidents of any nature caused by our defective products, are only those responsibilities that come under Italian law.
6-1624846
rev.14
230 volt mains voltage absent.
Emergency STOP present.
Fuse blown.
Power cable of motor not connected or faulty.
The photocell is not functioning or the beam is
interrupted.
The remote control has not been memorized or the
battery is flat.
The torque of the motor is insufficient.
The value of the obstacle sensitivity (if present) it is
not suitable for the installation.
The wire connection is not correct.
24V
Control unit
230V: 4 x 1,5 mm
2
24V: 2 x 1,5 mm
2
RX photocell
2
2
2
ITA
ENG
23/03/2016
PROBABLE CAUSE
TABLE - CABLES FOR 230V MOTOR
Black
Brown
Grey or Light blue
Yellow green
2 x 0,75 mm
2
TX photocell
2 x 0,75 mm
2
FRA
ESP
DEU
POR
SOLUTION
Check the main switch.
Check for any STOP selectors or commands.
If not used, check the jumper on the STOP input of
the control unit.
Replace with one of same value.
Connect the cable to the appropriate terminal
board or replace it.
Check the connection, remove any obstacle across
the beam.
Carry out the remote control learning procedure on
the control unit or replace the battery with a new
one.
Modify the value of the torque in the control unit.
Modify the value of the sensitivity in the control
unit, if possible.
Carry out the learning of the stroke with the BIOS2
/ BIOS2 ECO control unit.
Invert the connection of the cable of the motor
Phase 1
Phase 2
Common
Ground
230V: 4 x 1,5 mm
2
24V: 2 x 1,5 mm
2
11/20

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Xtilus 24v

Tabla de contenido