8.2_ Commissioning
Commissioning can only be performed after positive results of all
testing phases. Partial or "makeshift" commissioning is strictly pro-
hibited.
1_
Prepare the automation technical documentation (to be con-
served for at least 10 years), which must contain the follow-
ing documents: an overall layout diagram of the automation,
electrical wiring diagram, risk assessment and relative solu-
tions adopted, manufacturer's declaration of conformity for all
devices used (for T-SKY use the EC declaration of conformity
enclosed) copy of instruction manual for operation and the
automation maintenance schedule.
2_
Permanently affix a label or plate on the door, indicating the
operations for manual release and manoeuvres (use the fig-
ures in the "User Guide").
3_
Permanently affix a label or plate on the door with this image
(min. height 60mm).
4_
Affix a dataplate on the door, specifying at least the following
data: type of automation, name and address of manufacturer
(responsible for commissioning), serial number, year of con-
struction and CE mark.
5_
Compile the automation declaration of conformity and deliver
to the owner.
6_
Compile the manual "Instructions and warnings for automa-
tion operation" and deliver to the owner.
7_
Produce and supply the owner with the automation mainte-
nance schedule (containing all maintenance instructions for
all automation devices).
8_
Before commissioning the automation, ensure that the owner
is adequately informed in writing of all associated risks and
hazards (for example of the manual of instructions and warn-
ings for automation operation).
9_
OPERATION
Use of the device for purposes or in circumstances other than as
specified in this document is strictly prohibited. Note that this is a
mains-powered automatic device and must therefore be used with
caution. The following in particular is recommended:
1_
never touch the device with wet hands;
2_
disconnect the power supply before opening the controls box
and/or gearmotor;
3_
never pull the power cable to remove it from the socket;
4_
never touch the motor before ensuring it is completely cool;
5_
only move the door when it is completely visible;
6_
keep away from the operating range of the door when in
movement: wait until it is stationary;
7_
never allow children or animals to play in the vicinity of the
door;
8_
never allow children or unskilled persons to use the remote
control or other activation devices;
9_
perform periodic maintenance;
10_ in the event of a fault, disconnect the power supply and only
move the door manually when possible and in safety. Do not
intervene on the door; call an authorised technician for as-
sistance.
11_ never touch any mechanical part during operation;
12_ all actions not expressly envisaged in these instructions are
strictly prohibited.
10_
MAINTENANCE AND DISPOSAL
This chapter describes the procedures for drawing up a mainte-
nance schedule and disposal of T-SKY.
10.1_ Maintenance
To maintain a constant level of safety and guarantee maximum
lifetime of the entire automation, regular maintenance is required.
Maintenance must be performed in strict observance of
all safety instructions in this manual and in compliance
with current legislation and standards.
For devices other than T-SKY follow the respective maintenance
schedules.
1_
For T-SKY route maintenance is required within maximum six
months or 3000 duty cycles from the previous maintenance.
2_
Disconnect all electric power supply sources, including any
backup batteries.
3_
Check the condition of all automation materials, with special
attention to possible erosion or oxidation of structural parts;
replace any parts that do not guarantee total reliability.
4_
Check the state or wear of all moving parts: belt, carriage,
pinions and all door parts; replace any parts if worn.
5_
Reconnect the power supply sources and perform all checks
and tests as envisaged in paragraph "6.1 Testing".
10.2_
Special maintenance
If more complex operations are required on electro-mechanical
parts, the faulty part should be removed to enable repairs in the
manufacturer's workshop by technicians or other authorised cen-
tre.
10.3_
Disposal
T-SKY is made up of different types of material; some may be re-
cycled, such as steel, aluminium, plastic, or electric cables, while
others must be disposed of: batteries and electronic boards.
Some components may contain pollutant substances;
do not dispose of into the environment.Seek informa-
tion on recycling or disposal systems in observance of
current and local standards.
1_
Disconnect the automation and any backup battery from the
electrical mains.
2_
Disassemble all devices and accessories, in reverse order of
the procedures described in chapter "3 Installation".
3_
Separate where possible all parts which may or must be re-
cycled or disposed of differently, for example metal parts from
plastic parts, electronic boards etc.
4_
Sort and assign the separated materials to specialist waster
recovery and disposal centres in your local area.
11_
NOISE LEVELS
The noise emission level of the T-SKY operator, from the work po-
sition, is 52 dB(A).
T-SKY Series