Studer AJ Serie Manual De Usuario página 15

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

STUDER Innotec SA
Model
Inverter
Nominal battery voltage
Input voltage range
Continous power at 25ºC
Power 30 min. at 25ºC
Power 5 min.at 25ºC
Power 5 sec. at 25ºC
Maximum asymmetric load
Max. efficiency (%)
Cos φ max.
Detection of the load
Current of chort-circuit 2 sec. (exit)
Output voltage
Frequency
Distortion THD (resistive load)
Consumption Stand-by
Consumption „ON" no load
Overheat protection (±5ºC)
Short circuit protection
Reverse polarity protection by internal fuse
Deep discharge battery protection
Max. battery voltage
Acoustic alarm
General data
Weight
Dimensions hxwxl (mm)
Protection index IP
Certification ECE-R 10 (E24)
EC confirmity
Operating temperature
Relative humidity in operation
Ventilation forced
Acoustic level
Warranty
Approximate correction of Pnom
Recommended battery capacity
Length cables (Battery/left AC)
Options
Voltage max
Current max.
Solar regulator
Principle
Absorption voltage
Floating voltage
Remote control JT8 supplied with 5 m cable
AJ 1000-12
AJ 1300-24
12Vdc
24Vdc
10.5 – 16Vdc
21 – 32Vdc
(24Vdc max.)
(44Vdc max.)
800VA
1000VA
1000VA
1300VA
1200VA
2000VA
2200VA
2800VA
500VA
600VA
93%
0.1 – 1 up to 800VA
0.1 – 1 up to 1000VA
10Aac (20Aac*)
13Aac (26Aac*)
50Hz (60Hz*) ±0.05% (crystal controlled)
< 5% (at Pnom. & Uin nom.)
0.7W
1.2W
10W
Automatic disconnection with 2 restart attempts
125A
100A
Shut off at 0.87 x Unom, Automatic restart at Unom.
Shut off at >1.33 x Unom, Automatic restart at < Umax
Before low battery or overheating disconnection
8.5 kg
142x428x84
IP 30 conforms to DIN 40050
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 60950-1
> 5 x Pnom/Unom (recommended value in Ah)
1.5m /1m
AJ 1000-12
AJ 1300-24
25Vdc
45Vdc
25Adc
14.4Vdc
28.8Vdc
13.6Vdc
27.2Vdc
V3.01
AJ2100-12
12Vdc
10.5 – 16Vdc
(20Vdc max.)
2000VA
2100VA
2450VA
5000VA
1000VA
94%
92%
0.1 – 1 up to 2000VA
Adjustable: 1  20W
26Aac (52Aac*)
Sine wave 230Vac (120Vac*) ±5%
0.7W
13W
16W
Shut down at 75ºC, Auto-restart at 70ºC
Not protected
19 kg
IP 20 conforms to DIN 40050
-20ºC up to +50ºC
95% without condensation
From 45ºC ±5ºC
< 45 dB (with ventilation)
5 years
-1.5%/ºC as from +25ºC
AJ2100-12
25Vdc
3 floating stages (I/U/UO)
14.4Vdc
13.6Vdc
AJ
AJ 2400-24
24Vdc
21 – 32Vdc
(40Vdc max)
2000VA
2400VA
2800VA
5200VA
1200VA
94%
0.1 – 1 up to 2000VA
30Aac (60Aac*)
< 3% (at Pnom. & Uin nom.)
1.2W
16W
150A
18 kg
273x399x117
1.7m / 1m
AJ 2400-24
45 Vdc
30Adc
28.8Vdc
27.2Vdc
14