Diehl 775 Instrucciones De Montaje página 29

Ocultar thumbs Ver también para 775:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Deutsch
English
User guide for further Information is available at
https://www.diehl.com/metering/en/support-center/download-center/
6.1 Flow/return setting (optional ex works)
Optionally, the installation position of the meter can be set in-situ in loop 3
("3.5" page 38). Consequently installation in the inlet (flow) or outlet
(return) is possible.
This setting must be made prior to initial operation of the meter.
As supplied, the outlet (return) is pre-set and is shown as follows in the display.
To changeover, switch to the "OutLEt" window in loop 3 (see 9. Operation).
Pressing and holding the button for > 6 s changes the display/setting to
"InLEt".
This setting can be changed a total of 8 times by pressing the button.
The display changes during the 6 s.
This does not influence functioning.
Sequence during changing
If the button is pressed and then held for > 6 s, the meter performs the
command shown in the display.
Button pressed <3s
Setting and number of possi-
ble changes.
Button pressed >3s
-29-

Publicidad

Tabla de contenido
loading

Productos relacionados para Diehl 775

Tabla de contenido