Electrical installation
Mounting steps
Terminal data
E94AZRS0044
E94AZRS0104
E94AZRS0294
PE connection data
E94AZRS0044
E94AZRS0104
E94AZRS0294
Standard device
Cable X302
SSP94FF007
Mounting steps
Proceed as follows to connect the filter:
1. Connect the filter output cable (X302) to terminal X100 of the standard device.
2. Connect the mains cable to terminal X301.
3. Attach the supply−side PE conductor to the PE conductor screw using a ring or
fork−type cable lug.
– The PE connection must comply with EN 61800−5−1.
50
Max. conductor cross−section
2
[mm
]
[AWG]
2.5
14
4
12
10
Æ
[mm]
M5
Labelling
Description
1
Filter output conductor (lead with wire end ferrule, colour
BK)
2
3
PE
Output−side PE conductor (lead with M5 fork−type cable
lug, colour GN/YE)
l
Tightening torque
[Nm]
0.5 ... 0.6
8
1.2 ... 1.5
Starting torque
[Nm]
3.0
!
[lb−in]
4.4 ... 5.3
PH1
10.6 ... 13.3
!
[lb−in]
26.5
SW 8
EDK94AZRS DE/EN/FR/ES/IT 6.1