CODE (Hex)
D es crip t ion
PARAMETER CODES
019E
HaAN • Neutral current component 0 (DC) *
019F
HaAN • Neutral current component 1
01A0
HaAN • Neutral current component 2
01A1
HaAN • Neutral current component 3
01A2
HaAN • Neutral current component 4
01A3
HaAN • Neutral current component 5
01A4
HaAN • Neutral current component 6
01A5
HaAN • Neutral current component 7
01A6
HaAN • Neutral current component 8
01A7
HaAN • Neutral current component 9
01A8
HaAN • Neutral current component 10
01A9
HaAN • Neutral current component 11
01AA
HaAN • Neutral current component 12
01AB
HaAN • Neutral current component 13
01AC
HaAN • Neutral current component 14
01AD
HaAN • Neutral current component 15
Re g i ste r d es c ript io n
RECORDING DOWNLOAD
Prepare data for downloading
(according to the instrument model)
Delete recorded data (irreversible operation)
Read the record/s block previously downloaded (do not
consider the first word). The download block always
contains an integer record number.
For the block structure refer to the description of $F101
register.
Download and read the first/next record/s block.
Example 1 (BASIC instrument version)
Active&reactive powers, 16 values; the record length is
2(timestamp)+16 words=18($12); the download block will
contain 6 records.
Example 2 (ENH instrument version)
With 4 parameters enabled for recording: 24 values; the
record length is 2(timestamp)+24 words=26($1A); the
download block will contain 4 records.
Example 3 (ENH instrument version)
With 24 parameters enabled for recording: 72 values;
the record length is 2(timestamp)+72 words=74($4A); the
download block will contain 1 record.
Available only for ENH instrument version.
* The neutral current and the derivative parameters (AN, THDAN, HaAN) are not available if the set CT ratio or FSA value is different for each phase.
MODBUS RTU/ASCII, TCP
*
st
*
nd
*
rd
*
th
*
th
*
th
*
th
*
th
*
th
*
th
*
th
*
th
*
th
*
th
*
th
INTE GE R
F. code
Register
(Hex)
(Hex)
10
F000
10
F002
03 / 04
F100
03 / 04
F101
OU TP UTS
RE C -E NH
AL=Digital Output, Alarm
MAM=M in /Avg /Max
PLS=Digital Output, Pulse
E C =En e rgy cou n ters
AO=Analog Output
P rogra mma ble da ta
Words
$01=prepare AVG or MIN/AVG/MAX rec.
2
(according to the instr. model)
$02=prepare Energy rec. (only ENH instr.)
2
$01=delete AVG or MIN/AVG/MAX rec.
(according to the instr. model)
$02=delete Energy rec. (only ENH instr.)
$03=delete all rec. (only ENH instr.)
1+
Set the word number considering
that the download block must
124
contain an integer record number
+ 1 word. Each record contains
only the enabled parameters +
timestamp.
Example 1: 109 words=$006D
Example 2: 105 words=$0069
Example 3: 75 words=$004B
Set the word number considering
124
that the download block must
contain an integer record number.
Each record contains only the
enabled parameters + timestamp.
Example 1: 108 words=$006C
Example 2: 104 words=$0068
Example 3: 74 words=$004A
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
MAM
83