SOLUTION 3.
The appliance is installed with the ducting set output at the rear of the
stove (Fig. 3). In this case, the appliance heats the environment where it
is installed as well as the adjacent room via the top ducting.
Fig. 3
A+B + n bends = 4 m max
SOLUTION 4.
The stove is installed with the ducting set output on the right side (Fig.
4). A Y connector can be installed to heat to adjacent rooms as well as
the room that contains the stove.
Fig. 4
A+B + no. bends = 4 m max.
Wall ducting.
For effective channelled heat distribution, you must:
- Coat the pipe with insulating sheath 2 cm thick (e.g. mineral fibre,
ceramic fibre, rock fibre) in order to limit dispersions and to ensure an
adequately high air temperature.
- The insulating sheath must have a specific weight equal to or greater
than 50 kg/m³ with a minimum operational temperature limit of at
least 250°C. Thermal conductivity (100°C) ≤ 0.050 W/mK.
- The thermal insulation materials must have "AGI Q132" or "DIN
18895" labels.
- The total maximum length of the fan outflow flexible pipe must not
exceed 4 metres.
If the insulation material does not form part of flooring or
a
walls, it will be necessary to fix it to the surface using fixing
points spaced out at 30 cm intervals.
8
B
A
DT2034214-00
A
H07031720 / DT2002253 – 01
Opposite are some flexible pipe wall arrangement examples (Fig. 5-6).
Fig. 5
Hot air outlet heating area
An area where the presence of flammable objects (furniture, carpets,
curtains, etc.) or those affected by heat (wood, plastic,...) are forbidden
is to be provided around the hot air outlet.
Figure 7 displays the measurements relative to the safety area; this area
includes the 600 mm taken into account starting at the upper edge of
the outlet.
Fig. 7
600
Where there is flammable flooring, the hot air outlets must be
a
placed at a distance of at least 200 mm from the floor.
INSTALLATION
a
NIGHT MODE cannot be activated if the HOT AIR DUCTING SET
has been installed.
LIA MODEL.
- Remove the casing by following the instructions in the section
"CASING REMOVAL" of the instruction booklet included with the
product.
LISA MODEL.
- Remove the ceramic casing by following the instructions in the
chapter "INSTALLATION" of the casing instruction booklet.
Fig. 6
HOT AIR OUTLET VENT
600
DT2030172-00