Unscheduled maintenance

If replacing the electronic board , the user MUST set the
parameters as indicated in the table.
Type No. Description
Index showing boiler power in kW
PAR
01
0=24; 1 = 25; 2 = 30; 3 = 35; 4 = 40
Hydraulic configuration
0 = rapid
1 = storage tank with thermostat or
heating only
PAR
02
2 = hot water tank with sensor
3 = bithermic
4=instant with solar power input
5 = open vent
6 = boiler with heat pump
Gas Type Configuration
PAR
03
0 = G20; 1 = G31; 2 = G230
To enter "Parameter setting and display"refer to the indications
provided in the specific section.
Once the parameters in the table have been set, you must carry
out the entire phase of "Self-calibrating procedure" described
in the specific section.
If the gas valve and/or the ignition/detection electrode , and/or the
burner
, and/or the fan are replaced, the user must still carry out
the entire phase of "Self-calibrating procedure" described in
the specific section.
4.6

Malfunction codes and possible solutions

LIST OF MALFUNCTION/FAULT ALARMS
Type
No. Fault
ALL
01
Smoke thermostat
Low water pressure in
ALL
02
system
High water pressure in
ALL
03
system
Domestic hot water
sensor fault (return
ALL
04
sensor fault for T
models)
ALL
05
Delivery sensor fault
ALL
06
No flame detection
Sensor or safety
ALL
07
thermostat intervenes
Fault in the flame
ALL
08
detection circuit
90
Setting for
Brava
Slim HE ErP
24 25 30 35 40
0
1
2
3
4
0
0 or 1 or 2
Solution
- Contact the Technical
Assistance Centre
- Restore pressure
- Check for any leaks in the
system
- Empty the system via the
drain valve on the hydraulic
assembly and bring the
pressure to approximately
1.2 bar
- Check connections
- Check the sensor is working
- Check connections
- Check the sensor is working
- Check the integrity of the
electrode and check that it is
not grounded
- Check gas availability and
pressure
- Check the integrity of the gas
valve and the card
- Check the sensor or
thermostat connections
- Deaerate the system
- Check the bleed valve
- Replace the sensor or the
thermostat
- Check that the pump impeller
is not blocked
- Check the integrity of the
electrode and check that it is
not grounded
- Check the integrity of the gas
valve and the card
Type
No. Fault
No water circulating in
ALL
09
the system
ALL
10
Auxiliary sensor fault
Gas valve modulator
ALL
11
disconnected
Domestic hot water
ALL
12
sensor fault in tank mode
ALL
13
Smoke probe intervention
ALL
14
Smoke probe fault
Fan check cable
ALL
15
disconnected
ALL
18
Condensate level fault
Maximum number of
ALL
28
consecutive resets
reached
Return sensor fault (boiler
ALL
30
sensor fault for T models)
Fault due to low network
ALL
37
voltage
Incorrect network
ALL
40
frequency detected
Flame loss more than 6
ALL
41
consecutive times
ALL
42
Button fault
Open Therm
ALL
43
communication fault
Gas valve timeout fault
ALL
44
without flame
Lock for ∆T delivery/
ALL
56
return over max limit
(open vent)
Lock for flow temperature
ALL
57
(FT) check (open vent)
Self-calibrating procedure
ALL
62
is required
Incorrect positioning of
ALL
72
the delivery sensor
Second delivery sensor
ALL
74
fault
EV2 SGV current max/min
ALL
77
absolute limits error
EV2 SGV current upper
ALL
78
limit error
EV2 SGV current lower
ALL
79
limit error
Fault on the valve control
ALL
80
logic line/valve cable
damaged
EN
Solution
- Check the rotation of the
pump rotor
- Check the electrical
connections
- Replace the pump
- Check PAR 02 "hydraulic
configuration"
- Check the electrical
connection
- Check the electrical
connection
- Set the parameter
PAR 04 (Combustion
configuration) to 0
- Check the sensor is
working
- Replace the smoke probe
- Replace the smoke probe
- Check the electrical
connection of the smoke
probe
- Contact the Technical
Assistance Centre
- Check the connection
cable between the fan and
the board
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is
not clogged
- Wait 1 hour and try
unblocking the board
again
- Contact the Technical
Assistance Centre
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
- Check the voltage
- Contact your network
provider
- Contact your network
provider
- Check the ignition/
detection electrode
- Check the gas supply
(open valve)
- Check mains gas pressure
- Check that buttons are
working
- Check the OT electric
connection
- Check gas valve and board
- Contact the Technical
Assistance Centre
- Contact the Technical
Assistance Centre
- Carry out the self-
calibrating procedure (see
the specific section)
- Check delivery sensor
operation and position
- Check second delivery
sensor operation and
position
- Check gas valve and board
- Check gas valve and board
- Check gas valve and board
- Check gas valve and board