5.6 Front door opening and adjustment

Take note of the measurement "X" in Fig. 7 at the 4 corners of the door.
Unscrew the 4 nuts "A" and locknuts "B" to near the end of the thread. Make sure the door does not fall off the flaring of the 4 nuts "A".
Nut "A" must be accompanied step by step with its locknut "B".
To open the door to the right, tighten the right nuts "A" and locknuts "B" with each other, remove the left nuts "A" and open the door.
To open the door to the left, tighten the left nuts "A" and locknuts "B" with each other, remove the right nuts "A" and open the door.
Once the door is closed, refit it place, gradually tightening the 4 nuts and locknuts alternately. Lastly, check fume tightness in operation.
B
X
Fig. 7
Door opening can be either left or right by unscrewing the respective nut (e.g. A - Fig. 9).
• Door height adjustment is done with the nut (pos. 1); after adjusting, tighten the grub screws (pos. 2 - Fig. 10).
• Lengthwise adjustment is done with the screw pos. 3 - Fig. 10.
A
A
Fig. 9
A
1
3
cod. 3545456/0 - Rev. 00 - 08/2019
B
A
Fig. 8
2
Fig. 10