CAUTION
● This outdoor unit cannot collect more than the rated
refrigerant amount as shown by the nameplate on the
back.
● If the amount of refrigerant is more than that
recommended, do not conduct a pump down. In this
case use another refrigerant collecting system.
● Pay a special attention to the rotating of the fan while
operating.
Important Information Concerning Pump
Down
Observe the following items when using pump down operation
to recover the refrigerant.
(1) If the length of inter-unit tubing exceeds 30 m, pump down
cannot be used to recover the refrigerant.
(The overload protection device may be activated.)
(2) Short the "PUMP DOWN" pin (or press and hold the
"PUMP DOWN" button) on the outdoor unit PCB for 1
second or longer.
• During refrigerant recovery, LED 1 blinks and LED 2 is lit.
• Close the liquid-side valve during refrigerant recovery.
If the unit is operated for 10 minutes or longer with the
liquid-side valve open, operation will be stopped, although
no alarm will be displayed on the remote controller.
If this occurs, close the valve and restart operation.
(3) When the valve service port pressure is approximately 0.1
MPa, short the "PUMP DOWN" pin (or press the "PUMP
DOWN" button) again to end refrigerant recovery.
• In order to protect the compressor, do not continue
operating to generate a negative pressure in the inter-unit
tubing.
3 – 4 HP (Single-phase))
AUTO ADD (CN041)
PUMP DOWN (CN042)
EEPROM
The PUMP DOWN (CN042) pin is located at the right of the
outdoor unit PCB, as shown in the above figure.
5 HP (Single-phase), 3 – 6 HP (3-phase)
AUTO ADD PUMP DOWN
S003 S001
S002
The S005 (PUMP DOWN) button is located at the centre right of
the outdoor unit PCB, as shown in the above figure.
System address
(S002)
(S003)
LED2
LED1
S005
IC
001
11. HOW TO INSTALL WIRELESS REMOTE
CONTROLLER RECEIVER
NOT E
Refer to the Instruction Manual attached to the optional Wireless
Remote Controller Receiver.
12. MARKINGS FOR DIRECTIVE 97/23/EC
(PED)
Rating nameplate figure
SOURCE:
B:
220-240V
MAX ELECTRIC INPUT
TIME DELAY FUSE MAX SIZE:
UNIT PROTECTION: IPX4
Operating Spec. Area
Various
(Not for the PED)
DESIGN PRESSURE:
REFRIGERANT: R410A
NET WEIGHT
SERIAL NO. :
PROD. DATE :
CONTIENE REFRIGERANT R410A :
Tabulation of Various data
A
SPW-C256VH
B
3.88 kW,
C
19.0 A
D
E
F
G
1.7 kg
A SPW-C256VH8 SPW-C366VH8 SPW-C486VH8 SPW-C606VH8
B
3.04 kW,
C
6.8 A
D
E
F
G
1.9 kg
83
A: Model Name Various
~
50/60 Hz Various
C:
kW.
A Various
D:
A Various
HIGH SIDE:
E:
bar. Various
LOW SIDE:
F:
bar. Various
G:
kg (
lbs.) Various
Various (Not for the PED)
_ _ _ _ _ _
_ _ _ _ _ _
Serial Number Various
SPW-C366VH
SPW-CR486VH
220 – 240 V AC 50 Hz
4.28 kW,
21.0 A
25 A
41.5 bar
22.1 bar
2.6 kg
380 – 415 V 3N AC 50 Hz
3.42 kW,
5.82 kW,
8.2 A
13.0 A
16 A
41.5 bar
22.1 bar
2.8 kg
2.6 kg
Made in Japan
5.82 kW,
28.5 A
35 A
2.75 kg
6.68 kW,
15.0 A
20 A
2.75 kg