Uniteck UNISUN 50.12MS Manual Del Usuario página 30

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
PANEL TEST PROCESS (FOLLOWING)
CURRENT TEST IN SHORT-CIRCUIT
This test must be done with important irradiance conditions. The values displayed by a cloudy and grey weather
are thus irrelevant.
Set the multimeter on the A DC (continuous current) range corresponding to the panel intensity.
Connect the red cable to the « A » port (intensity) and the black to the "COM" port (common).
Connect the cables to the panel's connectors (red – red, black – black).
Place the solar panel perpendicular to the sun.
Result:
The displayed value must be equivalent (+/-20%) to the intensity in short circuit (Isc) of the panel. This value
can change according to the position to the sun.
You can find the Isc value in the technical specifications of this manual and in the back of each panel.
This test is valid if the displayed values match with the intensity of the panel (+/-20%).
TESTS CONCLUSION
30/49
TEST 1
X
X
TEST 2
X
X
www.uniteck.fr
RESULT
Panel anomaly
Renew test 1
Panel anomaly
Norma operation

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Unisun 100.12msUnisun 150.12ms

Tabla de contenido