For wall installation, install
the OLET 31 sensor 40 mm
from the ceiling on the centre
line of the heater.
For ceiling installation, in-
stall it above the heater,
and in line with the centre
line of the heater. Do not
install the
sensor anywhere else.
Output
kW
6,0
9,0
Power
Sauna heater's
connection cable
H07RN –F/ 60245
IEC 66
mm²
kW
400-415V 3N~
6,0
5 x 1,5
9,0
5 x 2,5
Connection of the sauna heater to the mains
The sauna heater must be connected to the mains by a qualified electrician and in compliance with current regulations. The
sauna heater is connected with a semi-permanent connection. Use H07RN-F (60245 IEC 66) cables or a corresponding type.
Other output cables (signal lamp, electric heating toggle) must also adhere to these recommendations. Do not use PVC
insulated cable as a connection cable for the sauna heater.
For more information installation user manual. www.tylohelo.com
Sauna heater safety clearances
MIN. mm
Sensor
OLET 31
A
100
490
10
MIN. mm
Sensor
OLET 31
A
100
490
10
Sauna room
Volume
Height
min.
max.
min. mm
5
10
1900
9
13
1900
Sauna heater's
Fuse
connection cable
H07RN –F/ 60245
A
3 x 10
3 x 16
40
A
100
A
100
Heater minimum clearances
From front
From side
A
D
mm
mm
100
300
100
350
Fuse
IEC 66
mm²
A
230V 3~
4 x 2,5
3 x 16
4 x 6
3 x 25
MIN. mm
40
Sensor
OLET 31
280
D
10
MIN. mm
Sensor
OLET 31
280
D
10
Amount of stone
To ceiling
F
mm
ca. kg
1070
38
1070
38
Sauna heater's
connection cable
H07RN –F/ 60245
IEC 66
mm²
230V-240V 1N~ / 2~
3 x 6
----------
Fuse
A
1 x 35
--------
4