Transponder card reader for installation outside rooms, KNX standard, 2
NO 4 A 24 V~ relay outputs, 2 inputs, power supply 12-24 V~ 50-60 Hz
and 12-24 V d.c. (SELV) - 3 modules.
The device, with transponder cards, enables controlling entry to the rooms where it is
installed externally. The transponder reader is provided with two relays to control the door
lock, to control a courtesy light, or for other uses; the device is moreover provided with
two inputs for connecting electrical equipment of the ON / OFF type (for example to con-
trol the switch for door opening and closing, a magnetic contact for signalling windows
open or closed, ceiling pull alarm, etc.). On the front of the reader there are four LEDs
each of which associated with an icon for signalling the following states:
- Access (entry allowed or entry denied);
- Guest status (room occupied or do not disturb);
- Call status (rescue request with bathroom ceiling pull-cord, room service call, etc.);
- Services status (make up room, etc.).
The transponder reader is able to dialogue with other KNX components via the specific
interface.
CHARACTERISTICS.
• Supply voltage:
- BUS: 29 V SELV
- 12-24 V ± 20% SELV
• Consumption:
- on the bus: 10 mA
- on the power supply (at 12-24 V ): 130 mA max
• Terminals:
- TP bus
- power supply (12-24 V )
- digital inputs for 2 NO or NC contacts (with no potential, SELV)
- outputs for 2 NO relays (24 V~ SELV 4 A cos 1; 24 V~ SELV 2 A cos 0.6)
• Frequency range: 13,553-13,567 MHz
• RF transmission power: < 60 dBμA/m
• Operating temperature: -5 °C - +45 °C (inside)
• This device contains only SELV circuits that must be kept separate from circuits with
dangerous voltage
OPERATION.
The configuration of the reader, physical address and parameters (NO or NC contact
inputs, normal or timed relay outputs, etc.) is done with the ETS software.
If the transponder reader is loaded with an incorrect ETS application, both the red LED
on the back of the device and the front LEDs 2, 3 and 4 will blink ("device type" error).
To restore the desired configuration, load the device with the correct ETS application.
The card is read by putting it in front of the reader that in sequence checks:
- "system code" (whether consistent);
- "date" field (if enabled, it checks whether the validity has expired);
- "password" (checks all the codes associated with it and enabled, such as guest code,
service code, timeframes).
IMPORTANT: The transponder card readers should be fed separately from all other
loads (electric locks, lamps, contactors, etc.) using a 16887 transformer dedicated
to them whose outputs will be used only for these two devices.
Important: The length of the cable for connecting the inputs must not exceed 30 m.
NB: In the phase of installation provide for cable connection lengths that allow extracting
the device from the flush mounting box so as to be able to access the configuration
button.
For the 12-24 V
power supply use 12/24 V d.c. power supplies or transformers with
secondary winding having extra low voltage (SELV) for continuous service; do not use
the voltage transformers for doorbells.
INSTALLATION RULES.
Installation should be carried out by qualified staff in compliance with the current regula-
tions regarding the installation of electrical equipment in the country where the products
are installed.
CAUTION: The tropicalised reader (.TR) complies with the same installation rules
as the traditional reader (indoor use at -5 °C - + 45 °C). It is not suitable for outdoor
installations where it is exposed to direct sunlight or rain, (even when combined
with a watertight IP55 cover) and for installations exposed to humidity and salt fog,
the use of the IP55 cover is nevertheless recommended.
CONFORMITY.
RED directive.
Standards EN 50491, EN 60669-2-5, EN 300 330, EN 62479, EN 301 489-3.
49400222D0 03 2010
Idea
Plana
16927
14457
14457.TR
FRONT VIEW.
1
2
3
4
LED STATUS.
• LED 1:
- steady green: signalling "Entry allowed" (the LED remains illuminated for approxi-
mately 3 s).
- blinking green: signalling if the timeframe is not valid (the LED blinks for approxi-
mately 3 s).
- steady red: signalling "Entry denied" (the LED remains illuminated for approxima-
tely 3 s).
- blinking red: signalling if the expiry date is not valid.
- steady amber: signalling if the system coding is not valid.
- blinking amber: signalling if the day of the week is not valid.
- blinking red/green: synchronize the device's internal clock.
• LED 2:
- red: signalling "Do Not Disturb".
- blinking red: signalling "Room occupied".
: amber - signalling "Room service call."
• LED 3
• LED 4: green - signalling "Make up room."
Note.
The meaning taken on by the LEDs depends on the subjects of communication (therefore the functions)
that are configured in the reader with the ETS software. For all the applications in which the device is
configured with different functions and LED indications to the standard ones, the customer can ask
Vimar to customize the symbols on the front of the reader with a laser.
REAR VIEW.
Configuration BUTTON
C NO
Relay 1
C
NO
Relay 2
Power supply
12-24 V
• Configuration BUTTON: button for switching between normal mode or programming
mode or detecting the physical address.
• LED off: "normal operation" indicator.
• Red LED: "addressing mode" indicator (the LED goes out automatically after program-
ming the physical address).
Vimar SpA declares that the radio equipment complies with Directive 2014/53/EU. The
full text of the EU declaration of conformity is on the product sheet available at the fol-
lowing Internet address: www.vimar.com.
REACH (EU) Regulation no. 1907/2006 – Art.33. The product may contain traces of
lead.
WEEE - Information for users
If the crossed-out bin symbol appears on the equipment or packaging, this means the product must not be included with
other general waste at the end of its working life. The user must take the worn product to a sorted waste center, or return it to
the retailer when purchasing a new one. Products for disposal can be consigned free of charge (without any new purchase
obligation) to retailers with a sales area of at least 400 m
tion for the environmentally friendly disposal of the used device, or its subsequent recycling, helps avoid the potential negati-
ve effects on the environment and people's health, and encourages the re-use and/or recycling of the construction materials.
LED
IN1
BUS line
IN2
Common
~
inputs
1 and 2
, if they measure less than 25 cm. An efficient sorted waste collec-
2
Viale Vicenza, 14
36063 Marostica VI - Italy
www.vimar.com

Publicidad

loading

Este manual también es adecuado para:

Eikon 20457.trArké 19457Arké 19457.trIdea 16927Plana 14457Plana 14457.tr