3.4 Interface configuration

MODBUS (RTU) Slave configuration
Interface Baud rate Data format Address
1 Start bit
8 Data bits
RS232
9600
Even Parity
1 Stop bit
1 Start bit
8 Data bits
RS485
9600
Even Parity
1 Stop bit
CR/LF Master configuration
Interface Baud rate Data format Address
1 Start bit
8 Data bits
RS232
9600
No Parity
1Stop bit
1 Start bit
8 Data bits
RS485
9600
No Parity
1Stop bit

3.5 Programming

1-247
1-247
1-99
The data sources can be set according to the
1-99
output operations set for the device. If the
concerned counter shows an overflow / underflow,
it does not send the data value, but +oooooo /
+uuuuuu.
Main interface programming
menu.
Interface protocols
MODBUS protocol
CR/LF protocol
Slave Address
CR/LF: 1 – 99
MODBUS: 1- 247
Cycle time (only for CR/LF)
0,5 – 9999,9 sec (ON)
0 sec
(OFF)
Data sources (only for CR/LF)
Main counter
Batch counter
Totalizer
Main and batch counter
Main counter and totalizer
Main menu for programming the
signal and control inputs
User input 1
User input 2
Triggering of the data
transmission via the user input;
possible cycle time
0, 5 sec
(possible only for CR/LF and
cycle time = 0)
Factory settings are highlighted
in grey.