IMMEDIATE
MESSAGE
AUTOMATIC ACTION
DISPLAYED /
FAULT
Stopping
DETECTED
production
Alarm
Yes
Flow
Alarm
Yes
Com. Failure
Alarm
No
pH Calibration
Alarm
No
pH Injection
Alarm
Yes
No water
Alarm
Yes
ORP Regulation
CAUSE
Stopping
pH
regulation
Insufficient water flow
Yes
through
circuit.
Loss of communication
between
No
board and the power
board of the electronics
unit.
pH
probe
Yes
calibrated.
Series of 5 unsuccessful
Yes
attempts to correct the
pH.
Insufficient amount of
Yes
water in the filtration
circuit.
ORP measurement out of
tolerance for 24 hours
No
(difference of ± 400 mV
compared to the ORP
setpoint).
CHECKS AND REMEDIES
Check that :
• the flow sensor is connected
to the electronics unit.
• the flow sensor is activated
Parameters
menu).
• the valves on the filtration
the
filtration
circuit are open.
• the
working correctly.
• the filtration circuit is not
blocked.
• there is enough water in the
pool.
the
control
Contact a professional.
incorrectly
Carry out a calibration of the
pH probe.
• Ensure the pH corrector
container is not empty.
• Carry out a manual injection
(menu «
Manual Injection
• Check the condition of the
filter
injection connector.
• Check the settings in the
«
pH Regulation - Setpoint
«
pH Regulation - Corrector
and «
menus.
• Carry out a calibration of the
pH probe.
Check that the filtration pump
is running correctly.
• Carry out a «
Test
• Carry out a calibration of the
ORP probe.
• Go to the «
ORP Prod.
that the production setpoint
is at 100 %.
»
-
Sensors
filtration
pump
is
pH
Regulation
-
»).
with
ballast
and
»,
»
»
Parameters - Volume
Electrolyse
».
Electrolysis -
» menu and check
OPTION TO
DEACTIVATE
VIA THE
MENU
«
Parameters -
»
Alarms
No
No
Yes
Yes
Yes
Yes
15