SOLUTION OF THE PROBLEMS
Problem
Water doesn't come out
from the tap after leaving
the action range
The water supply doesn't
close after leaving the
action range
Indication
The sensor flashes
continuously when it is
within the action range
The sensor doesn't flash
when it is within the action
range
The sensor flashes when it is
within the action range
Cause
Low battery load level
Unsuitable action range
Run up battery load level
The sensor is dirty or is
hidden
The sensor receives
reflections from a mirror or
another object.
The connectors between the
electronic part and the
solenoid valve are separated.
Debris, scaling or damages
in the solenoid valve.
The feeding pressure is
higher than 5 bar
Damaged electronic part
Debris, scaling or damages
in the solenoid valve
The sensor receives
reflections from a mirror or
another object.
Damaged electronic part
11
Solution
Replace the battery
Adjust the sensor sensitivity
Replace the battery
Clean or remove possible
interferences
Remove the cause of the
reflection
Connect the connectors
again
Disassemble the solenoid
valve, check the running
and clean or replace
eventually.
Reduce the feeding pressure
Replace the electronic part
Disassemble the solenoid
valve, check the running
and clean or replace
eventually.
Remove the cause of the
reflection
Replace the electronic part.