Intended Use; Technical Data; Function Of The Unit; The Leak Detector Operation - Rothenberger ROTEST Electronic 4 Instrucciones De Uso

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 16
1

Intended use

The ROTEST Electronic 4 is powered by two AA batteries. Take care to ensure the batteries are
inserted correctly. When replacing batteries please dispose of used batteries in accordance with
local regulations.
The ROTEST Electronic 4 will enable the operator to pin-point small combustible gas leaks. It
does not MEASURE gas levels.
Do not use the ROTEST Electronic 4 as a personal safety monitor.
Take extreme care when using the ROTEST Electronic 4, especially when gas is detected. If in
any doubt, open doors and windows to ventilate rooms under test, ensure people are not at risk
and call the Emergency Service Provider.
2

Technical Data

Power Supply .............................. 2 x AA-alkaline batteries
Sensor ......................................... Solid state semi conductor
Sensitivity .................................... < 50 ppm methane
Indicators ..................................... Audible: Variable tic rate
Warm-up ...................................... 20 seconds
Response Time ........................... <1 second
Duty Cycle ................................... Continuous
Battery Life .................................. 12 hours typical use
Dimensions .................................. Instrument = 180mm long, Probe = 430 mm long
Weight ......................................... Approx. 250gm
Operational Range: ...................... 0 - 40°C, 10% to 90% RH non-condensing
Gases detected include:
Acetone
Alcohol
Ammonia
Benzene
Butane
Ethylene
3

Function of the Unit

3.1

The leak detector operation

Warm up:
Switch the ROTEST Electronic 4 ON in fresh air (press and hold the on/off button
light will briefly illuminate. The top (red) LED will illuminate and the tic rate will be once a second.
The LEDs will then cycle for approximately 20 seconds to indicate the warm-up.
When the warm up is complete the bottom (green) LED will be illuminated and the ROTEST
Electronic 4 tic rate will be once every 2 seconds.
Normal operation:
The Green battery status LED will remain illuminated if the batteries have sufficient power to run
the ROTEST Electronic 4. If the Green LED is flashing the batteries in the ROTEST Electronic 4
must be replaced.
In fresh air the unit will tic once every two seconds.
If gas is detected the tic rate will increase, the Yellow LED's will illuminate.
Visual: Flashing multicoloured LEDs
Hydrogen
Gasoline:
Methane
Jet Fuel
Naphtha
Petrol
Natural Gas
Propane
Toluene
Industrial Solvents:
Lacquer
Thinners
ENGLISH
). The tip
7