The cylinder may be hot. Let it cool down before touching it or otherwise wear safety gloves.
All maintenance and/or service operations must be carried out by skilled and qualified staff who are
aware of the necessary precautions to be taken.
Before work is performed on the cylinder, check that the humidifier is isolated from the mains.
Remove the cylinder from the humidifier after it has been fully drained.
Check that the model and the input voltage of the replacement cylinder match those of the replaced cylinder.
Do not use cleaning agents or solvents to clean the plastic components.
To remove scaling, use a solution of acetic acid at a concentration of 20% and then rinse with water.
Run the equipment for one hour and then check for significant water leaks.
Every 15 days and after a period of max. the first 300 hours of operation inspect that the equipment works
correctly, check for significant water leaks, and monitor the overall condition of the enclosure. Check for arcing or
sparks forming among the electrodes during operation.
Check that the model and the input voltage of the replacement cylinder match those of the replaced cylinder.
Every three months and after max. 1000 hours of operation inspect that the equipment works correctly, check for
significant water leaks, and replace the cylinder if needed. Check for areas in the enclosure which have blackened
to excessive levels.If this is the case, check the scaling on the electrodes and replace them together with the o-rings
and the gasket in the cover, where necessary.
On a yearly basis and after max. 2500 hours of operation inspect that the equipment works correctly, check for
significant water leaks, monitor the overall condition of the enclosure, and check that no sensibly blackened areas
exist in the enclosure. Replace the electrodes with the o-rings and the gasket in the cover.
After five years and after max. 10,000 hours of operation replace the cylinder assembly.