Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.
1) Cut the pipes and the cable.
n Use the accessory piping kit or the pipes purchased
locally.
n Measure the distance between the indoor and the out-
side unit.
n Cut the pipes a little longer than measured distance.
n Cut the cable 1.5m longer than the pipe length.
2) Burrs removal
n Completely remove all burrs from the cut cross section
of pipe/tube.
n Put the end of the copper tube/pipe to downward direc-
tion as you remove burrs in order to avoid to let burrs
drop in the tubing.
3) Flaring work
n Carry out flaring work using flaring tool as shown below.
Pipe
Indoor unit
[kW(Btu/h]
Gas
≤ 5.6(19,100)
12.7(1/2)
<16.0(54,600)
15.88(5/8) 9.52(3/8)
≤ 22.4(76,400)
19.05(3/4)
Firmly hold copper tube in a bar(or die) as indicated
dimension in the table above.
4) Check
n Compare the flared work with figure below.
n If flare is noted to be defective, cut off the flared section
and do flaring work again.
[Unit: mm(inch)]
" A "
Liquid
Gas
Liquid
1.6~1.8
1.1~1.3
6.35(1/4)
(0.63~0.71) (0.43~0.51)
1.6~1.8
1.5~1.7
(0.63~0.71) (0.59~0.67)
1.9~2.1
1.5~1.7
9.52(3/8)
(0.75~0.83) (0.59~0.67)
Copper
Slanted Uneven Rough
tube
90°
Pipe
Point down
Bar
Bar
"A"
Copper pipe
Clamp handle
Smooth all round
Inside is shining without scratches.
= Improper flaring =
Inclined
Surface
damaged
Even length
all round
Installation Manual 17
Installation
Reamer
Handle
Yoke
Cone
Red arrow mark
Cracked Uneven
thickness