Section 3 RATING TAG CONVERSION
Figure 3
See Figure 3
Step 14
See Figure 3. Remove the data tag P/N 60011-10 or 60010-11 for their
respective gases. Remove label and place over the existing portion of
the tag. This label is pre-printed with all the correct information.
Step 15
information. Then place this tag below the updated rating tag on the
converted unit.
Figure 4
INLET PRESSURES:
Natural Gas
MAX - 14"WC (3.49kPa)
MIN - 5"WC (1.25 kPa)
Propane
MAX - 14" WC (3.49 kPa)
MIN - 11"WC (2.74 kPa)
All manuals and user guides at all-guides.com
E-6
Compact Unit Heater
Figure 5
NATURAL GAS MANIFOLD PRESSURES - IN.WG. (KPA)
MHU45/75
HSU 45/75
45/75
4.0 (0.99)*
*No adjustment required.
Figure 6
LP/PROPANE GAS MANIFOLD PRESSURES - IN.WG. (KPA)
MHU45/75
HSU 45/75
45/75
10 (2.49)*
*No adjustment required.
Fuel Conversion Manual
ALTITUDE FT. (M)
0-2000
2000-4500
(0-610)
(610-1370)
3.6 (0.89)
ALTITUDE FT. (M)
0-2000
2000-4500
(0-610)
(610-1370)
8.0 (1.99)