2.4
Residual risks
Risk of fatal injury due to contact voltages
XL Version: Removing the plug connections before disconnecting the device from the PV generator may lead to injuries
and damage the device.
During installation: Electrically disconnect the DC positive and DC negative from the protective earth (PE).
Disconnect the device from the PV generator using the integrated DC isolator switch.
Using a clip-on ammeter, check that there is no current in any of the DC cables before disconnecting the connect-
ors one after the other.
Risk of fire due to chemical corrosion!
The aluminium may be destroyed by the copper busbars in the presence of electrolytes (e.g. condensate).
Cable lugs must be suitable for the conductor material and copper busbars used.
When using aluminium cable lugs, use cable lugs with galvanic tin-plating or AL/CU cable lugs as well as suitable
AL/CU washers.
Lethal voltages are still present in the connections and cables of the housing even after the
component has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the component are touched.
Comply with all safety regulations and current technical connection specifications of the responsible power supply
company.
The component is only permitted to be opened or serviced by a qualified electrician.
Switch off the grid voltage by turning off the external circuit breakers.
Do not touch the cables and/or terminals/busbars when switching the device on and off.
Keep the component closed when in operation.
3
Assembly
3.1
Tools used
Code (s)
External hexagon
W
Internal hexagon
A
Torx
T
Slot
S
Tab. 1: Key and description of tool codes
3.2
Securing the component
↻ Adapter plate and short pedestal installed on the inverter.
1 Open connection area of the inverter. [See operating instructions for the
devices]
2 Remove component from the packaging and have the lock nut from the installa-
tion kit ready.
NOTE: Check that the adhesive seal of the adapter plate is not damaged or
dirty.
3 Insert DC cables of the component through the adapter plate (switch position:
front of the inverter).
4 Press the component onto the adapter plate using the threaded bolt.
5 Unscrew the lock nut on the threaded bolt and fit in diagonal pairs. [
6 Nm]
» Component is fitted onto the inverter. Continue with the connection of the
DC lead.
4
Installation
4.1
Opening the component
Page 4
Shape of the
connector
Tightening torque
Spanner size or number
Outer contour
Fig. 1: Form pattern
Fig. 2: Survey the DC connection
area
W_12 /
1
2
Nm
1
2
DC-side (-)
DC-side (+)
DC-Breaker