Technical Data; Electrical Data; Environmental Data; Environmental Conditions - Kaco 87.0-165 TL3 Instrucciones Breves

Ocultar thumbs Ver también para 87.0-165 TL3:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 15
5

Technical data

5.1

Electrical data

Input levels
Open circuit voltage/absolute max. input voltage (Vmax PV)
Max. input current (Inom PV)
max. short-circuit current [ISC PV (max])
General data
Protection class/overvoltage category
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Fitting for DC connection
Interface screw connections
Cable diameter for cable fitting
Torque for cable fitting
DC switch
Housing material
H x W x D
Weight
5.2

Environmental data

Environmental conditions

Ambient temperature from
Protection rating (KACO installation location)
Max. installation height
Relative humidity, non-condensing (in operation)
1,500 V
160 A
300 A
II/2
240mm² (4x AL or CU)
in accordance with local installation standards
16 - 28 mm
M40 (4x)
2x M16
6 mm²
(M16) 2.5 Nm
yes
AL
477 mm x 230 mm x 260 mm
8 kg
-25 °C - +60 °C
IP66
≤ 2000 m: max. 1500 V;
≤ 2500 m: max. 1395 V;
≤ 3000 m: max. 1320 V
95 %
Page 9

Publicidad

Tabla de contenido
loading

Tabla de contenido