System Startup - Ferroli DIVAtop HC Serie Instrucciones De Uso, Instalación Y Mantenimiento

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11
DIVAtop HC
F
I
R
A
B
fig. 20 - Gas valve
to
Pressure point upstream
B
Pressure point downstream
C
Modureg electrical connection
D
Protective cap
E
Minimum pressure adjustment
F
Modureg
G
Minimum pressure adjustment
I
Gas valve electrical connection
M
Pressure gauge
R
Gas outlet
S
Gas inlet
Heating power adjustment
To adjust the heating power, switch the boiler to TESTsec. 4.1 mode (see ). Press the
heating buttons (details 3 and 4 - ) to fig. 1increase or decrease the power (min. = 00
- max. = 100). Press the RESET button within 5 seconds and the max. power will remain
that just set. Exit TEST mode (see sec. 4.1).
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 4.1). Press the
DHW buttons (details 1 and 2 - ) to increase or decrease the powerfig. 1 (min. = 00 -
max. = 60). Press the RESET button within 5 seconds and the ignition powerwill remain
that just set. Exit TEST mode (see sec. 4.1).
4.2 System start-up
B
Checks to be made at first ignition, and after all maintenance operations that
involved disconnecting from the systems or an intervention on safety devices
or parts of the boiler:
Before lighting the boiler
Open any on-off valves between the boiler and the systems.
Check the tightness of the gas system, proceeding with caution and using a soap
and water solution to detect any leaks in connections.
Check the correct preloading of the expansion tank (ref. sec. 5.3)
Fill the water system and make sure that all air contained in the boiler and the sys-
tem has been vented by opening the air vent valve on the boiler and any vent valves
on the system.
Make sure there are no water leaks in the system, hot water circuits, connections or
boiler.
Check the correct connection of the electric system and the functioning of the earth
system. l
Check that the gas pressure value for heating is as required.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler
Checks during operation
Ignite the appliance as described in sec. 2.3.
Check the airtightness of the fuel circuit and water systems.
Check the efficiency of the flue and air-fume ducts while the boiler is working.
Check that the water is circulating properly between the boiler and the systems.
Make sure that the gas valve modulates correctly in both the heating and hot water
production phases.
Check the proper ignition of the boiler by performing various tests, turning it on and
off with the room thermostat or remote control.
Make sure that the fuel consumption indicated on the meter corresponds to that giv-
en in the technical data table in sec. 5.3.
Make sure that with no call for heating the burner correctly ignites on opening a hot
water tap. Check that during heating operation, on opening a hot water tap, the heat-
ing circulator stops and there is a regular production of hot water.
Check the parameters are programmed correctly and perform any required custom-
ization (compensation curve, power, temperatures, etc.)
+
D
M
E
G
S
C
cod. 3540S840 - 02/2010 (Rev. 00)
4.3 Maintenance
Periodical check
To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly check, providing for the following:
The control and safety devices (gas valve, flowmeter, thermostats, etc.) must func-
tion correctly.
The fume exhaust circuit must be perfectly efficient.
(Sealed chamber boiler: fan, pressure switch, etc. - The sealed chamber must be
tight: seals, cable glands, etc.)
(Open chamber boiler: anti-backflow device, fume thermostat, etc.)
The air/fume terminal and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. For cleaning do not
use chemical products or wire brushes.
The electrode must be free of scale and properly positioned.
The gas and water systems must be tight.
The water pressure in the cold water system must be approx. 1 bar; otherwise bring
F
it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
The gas flowrate and pressure must match that given in the respective tables.
A
The boiler casing, control panel and aesthetic parts can be cleaned with a soft
damp cloth, if necessary soaked in soapy water. Do not use any abrasive de-
tergents and solvents.
Opening the casing
To open the boiler casing:
1.
Undo the screws A (see fig. 21).
2.
Turn the casing (see fig. 21).
3.
Lift the casing.
B
Before carrying out any operation inside the boiler, disconnect the power supply
and close the gas cock upstream
A
1
Combustion analysis
1.
Insert the probe into the flue;
2.
Check that the relief valve is connected to a drain funnel;
3.
Activate TEST mode;
4.
Wait 10 minutes for the boiler to stabilize;
5.
Take the measurement.
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the
display will flash together with the fault symbol (detail 22 - fig. 1) indicating the fault code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation just press the RESET button (detail 8 - fig. 1) for 1 second or RESET on the
optional remote timer control if installed; if the boiler fails to start, it is necessary to first
eliminate the fault.
Other faults (marked with the letter "F") cause temporary shutdowns that are automati-
cally reset as soon as the value returns within the boiler's normal working range.
A
fig. 21 - Opening the casing
EN
3
2