(7) Push the 9mm (30�) o/dx 6mm (20�) i/d tube onto the reservoir and the pump. Secure with
cable-�es. Ensure length is under 1.5 meters (5 feet).
(8) Connect your 9mm (30�) o/d x 6mm (20�) i/d silicone discharge tube to the outlet barb on
the pump and secure with a cable �e. Channel discharge tube to an appropriate drain avoiding
restric�ons.
(9) A high-level alarm switch should be wired into the cooling signal wire, to prevent the
con�nued opera�on of the air condi�oning unit in the event of the pump failing.
(10) Test pump opera�on by pouring water into evaporator tray. Check for leaks.
< 1.5m (5 ft)
< 8m
(26ft)
< 25m
(82ft)
Power:
(L) Live: Brown
(N) Neutral: Blue
(E) Earth: Green & Yellow
Alarm/volt free:
(N.C.) Normally closed: Purple
(COM) Common: Red
(N.O.)Normally open: Green
6