Descargar Imprimir esta página
Emerson ALCO CONTROLS ESC Serie Manual De Instrucciones
Emerson ALCO CONTROLS ESC Serie Manual De Instrucciones

Emerson ALCO CONTROLS ESC Serie Manual De Instrucciones

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 4

Enlaces rápidos

G e n e r a l i n f o r m a t i o n :
ESC Series Coils are for use with certain EMERSON products.
Coil
Voltage
24 VAC ±10 %
ESC-24VAC
(17 VA, 8 W)
230 VAC ±10 %
ESC-230VAC
(17 VA, 8 W)
120 VAC ±10 %
ESC-120VAC
(17 VA, 8 W)
24 VAC ±10%
ESC-M24VAC
(25 VA, 16 W)
24 VDC ±10 %
ESC-24VDC
(17 W)
24 VAC ±10 %
ESC-W24VAC
(38 VA, 18 W)
230 VAC ±10 %
ESC-W230VAC
(38 VA, 18 W)
NOTE 1:
MOPD will decrease if the coils will be used at 60 Hz frequency. Also follow the operating instructions of the used devices.
NOTE 2:
1) OM3-02P used with R290 (A3). Installation only in a non-explosive environment.
NOTE 3:
2) Temperature impacts MOPD and coil use. Please refer to Technical Information of the connected valve.
S a f e t y i n s t r u c t i o n s :
• Read operating instructions thoroughly. Failure to comply can result in device failure,
system damage or personal injury.
• This product is intended for use by qualified personnel having the appropriate
knowledge and skills like trained according to EN 13313 or a specific training for
flammable refrigerants.
• The coil should be fused in accordance with local codes. Electrically ground the valve
body.
• Do not exceed the specified maximum ratings for temperature, voltage and current.
• Ensure that the system piping is grounded.
• Before installation or service disconnect all voltages from system and device.
• Observe and avoid mechanical damage of component housing.
• Do not energize coil unless it is attached to the device.
• Ensure that design, installation and operation comply with European and national
standards/regulations.
• Disposal: Electrical and electronic waste must NOT be disposed of with other
commercial waste. Instead, it is the user responsibility to pass it to a designated
collection point for the safe recycling of Waste Electrical and Electronic Equipment
(WEEE directive 2012/19/EU). For further information, contact your local environmental
recycling center.
I n s t a l l a t i o n o f c o i l s : ( F i g . 1 a , 1 b , 1 c )
• Mount O-ring with smaller diameter (1) over enclosing tube.
• Place coil over the enclosing tube and press it down by hand.
• Place the black retainer (2) on the upper visible end of the enclosing tube. The two slots
of the retainer fit to stumps of ESC coil. (5)
• Insert O-ring with larger diameter (3) inside of the orange screw cap
• Press coil well down and tight the screw cap (4) over the retainer firsthand tight and then
with torque 0.5 - 0.6 Nm in order to provide IP65 protection. Use spanner size 27 mm.
E l e c t r i c a l c o n n e c t i o n :
• Entire electrical connections have to comply with local regulations.
• Before energizing the device, be sure that the source voltage and frequency matches
that on the coil label.
• Ensure that the cables are mounted without tension; always leave the cable a bit loose.
• Ensure that cables are not mounted near sharp edges.
• Do not bend or mechanically stress the cable outlet, maintain a clearance of 20 mm to
neighboring parts.
• Ensure, that the plug (with cable) is correctly placed and tighten.
Emerson Climate Technologies GmbH
Pascalstrasse 65 I 52076 Aachen I Germany
O P E R A T I N G I N ST RU C T I O N S
Approved
Frequency
Markings
50(60) Hz
,
50(60) Hz
,
50(60) Hz
,
50(60) Hz
,
--
,
50(60) Hz
,
50(60) Hz
Coils ESC Series
Expansion
Valves
110RB
EX2
CX2
200RH
200RB
Standard plug and cable assembly (ASC-N...)
Brown and blue color wires (BN & BL Fig. 2) to be connected to the power supply and
yellow/green color wire to the ground. Connect pre-wired plug to the coil and tighten
screw with 0.2 Nm.
Wiring with DIN Plug (Fig. 3)
Cable with three wires has to be connected to terminal 1 and 2 and
plug terminal box. Connect pre-wired DIN-plug to the coil and tighten screw with 0.2 Nm.
S e r v i c e / M a i n t e n a n c e :
• WARNING: ESC coils are intended for continuous-duty, which when energized for
an extended period of time, it becomes hot. This is normal. Do not touch the coil
during operation. Wait for coil temperature to cool down before attempting to
dissemble it, or use gloves, failure to do so could lead to injury.
• Disconnect electrical power before service.
Dismantle of ESC: unscrew the screw cap (4) and pull the coil with retainer (2) out.
Remove smaller O-ring.
Replacement of ASC.../ ASC3... with ESC series:
-
Dismantle ASC... by opening blue clip (Fig.4)
-
Dismantle ASC3...: see Fig. 5. Remove smaller O-ring.
• To ensure proper function and protection, only O-rings approved for ESC coils may be
used. Any existing O-rings must be replaced.
T e c h n i c a l D a t a :
Coil
ESC-24VAC
ESC-230VAC
ESC-120VAC
ESC-24VDC
ESC-W24VAC
ESC-W230VAC
ESC-M24VAC
Supply voltage variation
Ambient temperature range
Protection class
Vibration resistance
www.climate.emerson.com/en-gb
Devices
Solenoid Valves
240RA
200RC
M36
540RA
2
2
Inrush current
with EMERSON offered Cables and plugs)
OI_ESC_A1_EN_DE_FR_ES_IT_RU_Rev05_866915.docx
EN
Oil management
OM3/4
OM5
OM3-02P*
1
(ground) on the
Holding current
(A)
(A)
2.23
0.57
0.22
0.052
0.48
0.11
-
0.72
2.7
1.2
0.52
0.11
1.7
1.05
±10 %
-40...+60 °C
IP65
(properly installed on enclosing tube
0.7 g 10 ... 200 Hz
Date: 16.05.2022

Publicidad

loading

Resumen de contenidos para Emerson ALCO CONTROLS ESC Serie

  • Página 1 O P E R A T I N G I N ST RU C T I O N S Coils ESC Series G e n e r a l i n f o r m a t i o n : ESC Series Coils are for use with certain EMERSON products. Devices Expansion...
  • Página 2 B E T R I E B S A N L E I T UN G Spulen Baureihe ESC B e s c h r e i b u n g : ESC Spulen sind für die Verwendung mit verschiedenen EMERSON Produkten vorgesehen. Geräte Expansions- Ölmanagement...
  • Página 3 Bobines Série ESC I n f o r m a t i o n s g é n é r a l e s : Les bobines de la série ESC sont destinées à être utilisées avec certains produits EMERSON. Appareil Vanne détendeur...
  • Página 4 I N S T R U C C I O N E S D E F U N C I O NA M I E N T O Bobinas de la serie ESC I n f o r m a c i ó n g e n e r a l : Las bobinas de la serie ESC son válidas para ciertos productos EMERSON. Componente Válvula de Sistema de control de nivel de Electroválvulas...
  • Página 5 I N S T R U Z I O N I O P E R A T I V E Bobine Serie ESC I n f o r m a z i o n i g e n e r a l i : Le bobine serie ESC possono essere utilizzate per i prodotti vari EMERSON. Dispositivo Valvole di...
  • Página 6: Руководство По Эксплуатации

    Р У К О В О Д СТ В О П О Э К С П Л УА Т А Ц И И Катушки ESC О б щ а я и н ф о р м а ц и я : Катушки серии ESC предназначены для определённых продуктов EMERSON. Устройство Pасширительны...
  • Página 7 Fig./ Pис. 1a: Fig./ Pис. 1c: Fig./ Pис. 1b: Fig./ Pис. 2: ASC-N… Fig./ Pис. 3: DIN-Plug Fig./ Pис. 4: ASC- … Fig./ Pис. 5: ASC3 Emerson Climate Technologies GmbH www.climate.emerson.com/en-gb Date: 16.05.2022 Pascalstrasse 65 I 52076 Aachen I Germany OI_ESC_A1_EN_DE_FR_ES_IT_RU_Rev05_866915.docx...

Este manual también es adecuado para:

Alco controls esc-24vacAlco controls esc-230vacAlco controls esc-120vacAlco controls esc-m24vacAlco controls esc-24vdcAlco controls esc-w24vac ... Mostrar todo