TX207
EN
Quick Start Guide
HMI — TX207
Additional Documents
The following additional documents are available online at
Data sheet
Declarations of conformity
Approvals
For your safety
Intended use
The HMI (Human Machine Interfaces) TX207 is used to control, operate and
monitor machine processes.
The device may only be used as described in this manual.
Any other use is not in accordance with the intended use. Turck accepts no li-
ability for any resulting damage.
General safety instructions
The device may only be assembled, installed, operated, parameterized and
maintained by professionally-trained personnel.
The device meets the EMC requirements for industrial areas. When used in
residential areas, take measures to avoid radio interference.
The device is a protection class III device according to IEC/EN 61140 or class 2
according to UL standard.
The device may only be used in accordance with applicable national and
international regulations, standards and laws.
Product description
Device overview
See fig. 1
Functions and operating modes
The TX207 combines the functions control, operation and monitoring in a full-
scope control thanks to the CODESYS V3 PLC with integrated visualization. The
CODESYS 3 control of the TX207 has the functions PROFINET controller, Ether-
Net/IP scanner and Modbus TCP as well as Modbus RTU master. Additionally the
TX207 can be used as Modbus TCP as well as Modbus RTU slave.
Additional functions
Ethernet TCP/IP or UDP/IP communication
OPC-UA server and client
Serial communication via RS232, RS485 and RS422
Mounting
See fig. 2 and 3
A = TX200
B = installation cut-out (176 × 136 mm)
Tighten the screws until the corners of the frame rest on the panel. The maxi-
mum tightening torque is 0.75 Nm.
TX...
Number of brackets included in delivery
TX207
4
Connecting
Connectors and slots
See fig. 4
Connector
Function
24 V
Power supply
X2
RS422/485 + CAN (COM2/CAN0)
X3
RS422/485 + CAN (COM3/CAN1)
X4
RS232 + RS232 (COM1/COM4)
X5
USB port
X6
USB port
X7
Ethernet port 0 (10/100 Mbps)
X8
Ethernet port 1 (10/100 Mbps)
S1
RS485 + CAN port configuration (DIP)
S2
RS485 + CAN port configuration (DIP)
Power supply
www.turck.com
DANGER
Wrong selection of power supply
Danger to life due to overvoltage and electric shock!
Only operate the device in a SELV or PELV circuit according to IEC/EN 61131
or IEC/EN IEC 61010-2-201 or on Class 2 voltage sources according to UL
standard.
Connect the device to the voltage supply according to "Wiring diagrams".
Grounding the device
Ground the device in accordance with the applicable installation regulations
and standards.
Connect terminal 3 on the power supply terminal block to ground. The mini-
mum conductor cross-section for the ground connection is 1.5 mm².
Serial interfaces/CAN interface
RS485/CAN (X2 and X3)
See „Wiring diagrams"
RS232 (X4)
See „Wiring diagrams"
RS485 (CAN port configuration – DIP switches S1 and S2)
Position
1
2
3
4
5
6
Maintenance
The devices must be cleaned at regular intervals with a damp cloth.
Repair
The device must not be repaired by the user. The device must be decommis-
sioned if it is faulty. Refer to our return acceptance conditions when returning
the device to Turck.
Disposal
The device is equipped with a rechargeable lithium battery, which is not user
replaceable.
For disposal, open the back of the device and remove the battery.
The device the lithium battery must be disposed of properly in accor-
dance with WEEE Directive 2012/19/EU and does not belong in normal
household waste.
Meaning
CAN terminating resistor
CAN terminating resistor
RS485 half duplex
RS485 half duplex
RS485 terminating resistor
RS485 terminating resistor