Descargar Imprimir esta página

LEM A 6403 06311 Manual De Instrucciones página 14

Adapter para medición de puesta a tierra sin estacas

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Operation
Clamp both transformers around the ground conductor to be tested (try to have a
distance > 10 cm between the clamps for optimal results.
Pushing the START-button will display the value of RE.
Note:
In this particular mode the values of RH and RS have no meaning!
Settings on the tester:
Refer to section "operation" in the testers instruction manual.
The rotary switch of the tester must be in the
R
3pole position.
E
- Um
set Test Voltage to 48V (standard value)
- Rk
set compenstion resistance to 0,000 Ohms
- I
set transformer ratio to 1000 (standard value)
- R*
set to OFF (no meaning in this mode).
14
Earth
Adapter for stakeless ground testing
A640311 GA1 Z REV 1

Publicidad

loading