Operation Instruction
Attention: >LIMIT4000Ω displayed on LCD warns that the auxiliary earth resistance of the auxiliary
earth rods is so high that the current can not flow across the meter. Check if the test leads become
loose and the amount of the earth resistance of the auxiliary earth rods. In a measurement, test
leads twisted together or becoming contacted each other will cause error in the measurement;
therefore, make sure that a measurement is done when the test leads are separate. Besides, too
much auxiliary earth resistance will bring unacceptable error to the measurement, therefore,
respectively bury deep auxiliary earth rods such as P and C in too wet sites and ensure good
connection in each joint.

4.4. Data Storage

The meter is capable of storing up to 100 groups of measurement data, which will not be lost even
in case of power cuts.
(1) When the meter is standing by, press MEMO to call the display for data storage, with "MEMO"
glittering at the lower right corner of LCD; should the existing memory has been used for storage of
other data, "USED" would be shown on LCD when pressing MEMO to exit data storage.
(2) Press "ENTER" briefly to switch A bit of a memory position and 10-bit and the memory position
can be scanned by pressing "
" or "
".
(3) Press "ENTER" for 2 seconds to store a group of data in a memory and in case that there are
data stored before in the memory, the current data will cover the previous data.
45