(1) Follow local codes and regulations when sizing conductors. Minimum wire sizes are stated above.
(2) When transmitting cable length is longer than 262ft. (80m), a larger wire size should be selected.
(3) Install main switch and ELB for indoor and outdoor unit separately.
Select the high response type ELB that is acted within 0.1second.
(4) If auxiliary heater is required and already installed on indoor unit, power source cable should be installed separately
and the size should be selected in accordance with UL.
5.2 Change of Static Pressure
The static pressure can be selected by changing Dip Switches on electric board.
Static Pressure Setting:
Dip Switch S2
Blower Speed Tap
Setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
NOTE: Symbol "
" indicates the position of the dip switch.
Symbol "
" indicates any position of ON or OFF.
6. Test Run
Please perform test run according to installation manual of outdoor unit.
Fan Speed Select
Medium Low
2
(Default setting)
3
Medium
4
Medium High
5
High
Installation and Maintenance
Static Pressure
(W.C.[kPa]) 24K
0.18[0.045]
0.25[0.08]
0.58[0.145]
0.8[0.2]
9
Static Pressure
Static Pressure
(W.C.[kPa]) 36K
(W.C.[kPa]) 48K/60K
0.24[0.057]
0.28[0.07]
0.4[0.1]
0.58[0.145]
0.58[0.145]
0.8[0.2]
0.4[0.1]
0.8[0.2]