102 PSI and TO is set for 3.0 PSI, then
the highest value for the Low Pressure
setpoint would be 99 PSI.
The lowest value for the Low Pressure
o
setpoint = Pm "Minimum Pressure Alarm"
setpoint plus 2 times TO "Tolerance" If
Pm is set for 80 PSI and TO is set for 3.0
PSI, then the lowest value for the Low
Pressure setpoint would be 86 PSI.
4. Scroll up (+)
until the number is set to the value required to
maintain control of for your air system. Press
the enter
button to confirm your selection.
You should be returned to the T01 home screen
and values just entered should appear next to
the PL parameter.
MINIMUM PRESSURE ALARM SETTINGS
1. From the T01 home screen scroll up (+)
or scroll down (-)
highlight 03- Pm (Minimum Pressure Alarm).
Minimum Pressure Alarm Setting
2. The default setting for this parameter is 80 PSI.
The 80 PSI indicates the Minimum Low Pressure
Setpoint that is used to alarm if the pressure in
the air system is low when the Table is active.
3. Press the enter
Minimum Low Pressure Setpoint setup screen.
The flashing cursor should be displayed
highlighting the 80 PSI. The values for this
parameter are:
The lowest Minimum Pressure Alarm
o
setpoint = "The minimum range of the
pressure transducer used.
The highest Minimum Pressure Alarm
o
setpoint = "The value from the Table PL –
Low Pressure Setpoint" minus 2 times TO
"Tolerance""
If PL in Table 1 (T01) is set for
100 PSI and TO is set for 3.0
PSI, then the highest Minimum
Pressure setpoint would be 94
PSI
All manuals and user guides at all-guides.com
or scroll down (-)
to move the cursor to
button to display the
4. Scroll up (+)
until the number is set to the value required to
maintain control of for your air system. Press
the enter
You should be returned to the T01 home screen
and values just entered should appear next to
the Pm parameter.
5. After you have completed adjusting the settings
on the T01 screen, press the escape
button to return to the page selection screen.
6. After you have returned to the page selection
screen press the escape
to the main screen.
TOTAL UNIT RESET AND DEFAULT VALUES
If at any time there is a requirement to reset all the
parameters and internal memory values to factory
default, this can be accomplished by using the following
procedure.
1. Press the menu
the Access Code Screen.
Access Code Screen
2. Enter the access code '9750' but do not press
the enter
character "0" is flashing.
3. When the flashing cursor is highlighting the last
"0", press and hold the STOP
for 10 seconds. After 10 seconds, the controller
will reset and re-initialize.
4. All parameters, values and options will be reset
to default and the internal permanent memory
will be cleared and reset. The Default Parameters
for all X4I settings are shown in the following
lists.