DRE
REGULADOR DIGITAL DE VENTILADOR,
MONTAJE EN CARRIL DIN
HOLDING REGISTERS
1
Device slave address
2
Modbus baud rate
3
Modbus parity mode
4
Device type
5
HW version
6
FW version
7
Operating mode
8
Output overwrite
9—10
11
Umin
12
Umax
13
Regulation type
14
Start-up type
15
Kick start time
16
NBT
17—20
21
Output overwrite value
22—30
Más información sobre el protocolo de comunicación Modbus es accesible en:
COILS
1
L1 output relay
* Us – la tensión de alimentación de la red eléctrica (230 VAC ±10 %).

TRANSPORTE Y ALMACENAMIENTO

MIW-DRE-ES-000 - 01 / 03 / 2021
Data type
Description
unsigned int.
Modbus device address
unsigned int.
Modbus communication baud rate
unsigned int.
Parity check mode
unsigned int.
Device type (Read only)
unsigned int.
Hardware version (Read only)
unsigned int.
Firmware version (Read only)
unsigned int.
Enables Modbus control
Enables direct control over the output.
unsigned int.
Active only if holding register 7 is set to
1.
Reserved, returns 0
Minimum output value selection. Active
unsigned int.
only if holding register 7 is set to 1.
Maximum output value selection. Active
unsigned int.
only if holding register 7 is set to 1.
Regulation type (Normal / Inverse)
unsigned int.
selection. Active only if holding register
7 is set to 1.
Start-up type selection. Active only if
unsigned int.
holding register 7 is set to 1.
Kick start duration selection. Active only
unsigned int.
if holding register 14 is set to 0.
Sets the network bus termination
unsigned int.
resistor. Active only if holding register 7
is set to 1.
Reserved, returns 0
Output overwrite value. Active only if
unsigned int.
holding registers 7 and 8 are set to 1.
Reserved, returns 0
Data type
Description
Unregulated output relay control. Active
bit.
only if holding registers 7 and 8 are set
to 1.
Evite choques y condiciones extremas, almacene en el embalaje original.
www.sentera.eu
volver al índice
Data
Default
1—247
0—6
0—2
DRE-1 = 3008
XXXX
XXXX
0—1
0—1
30—65
75—100
0—1
0—1
3—9
0—1
0,
30—100
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
Data
Default
0—1
Values
1
0 =
1 =
2 =
19.200
2
3 =
38.400
4 =
57.600
5 =
115.200
6 =
230.400
0 =
1
1 =
2 =
0 x
HW version 1.0
0100 =
0 x
FW version 1.2
0120 =
0 =
Standalone mode
0
1 =
Modbus mode
0 =
Disabled
0
1 =
Enabled
30 =
30 % Us (70 VAC)
30
65 =
65 % (150 VAC)
75 =
75 % Us (170 VAC)
100
100 =
100 % Us (230 VAC)
0 =
Normal
0
1 =
Inverse
0 =
Kick start
0
1 =
Soft start
5
5 =
0 =
Disconnected
0
1 =
Connected
0 =
0 % Us (0 VAC)
0
30 =
30 % Us (70 VAC)
100 =
100 % Us (230 VAC)
Values
0 =
1
1 =
10 - 11
4.800
9.600
8N1
8E1
8O1
5 s
Off
On