DRE
REGULADOR DIGITAL DE VENTILADOR,
MONTAJE EN CARRIL DIN
ESTRUCTURA DE MENÚ
>3 s
ON/OFF
Posición
- 9
Posición
- 0

MAPAS DE REGISTROS MODBUS

INPUT REGISTERS
1
Output value
2
Current output step
3
Umin
4
Umax
5
Regulation type
6
Start-up type
7
Kick start time
8
Unregulated output state
9
10
Unit status
MIW-DRE-ES-000 - 01 / 03 / 2021
NBT
Duración de 'kick
start'
Kick start
Tipo de regulación
Umin
Tensión
de salida
Umax
Data type
Description
unsigned int.
Current output value
unsigned int.
Current output step
unsigned int.
Minimum output value
unsigned int.
Maximum output value
unsigned int.
Regulation type (Normal / Inverse)
unsigned int.
Start-up type
unsigned int.
Kick start duration
unsigned int.
Unregulated output state
Reserved, returns 0
unsigned int.
Current controller working state
www.sentera.eu
volver al índice
1 - Conectada
0 - No conectada
0 - 1
9—9 s
3—3 s
3...9
1 – Soft start
0 – Kick start
0 - 1
1 – Inversa
0 – Normal
0 - 1
4 – 45,6 %,
9 – 65,0 %,
3 – 41,7 %,
8 – 61,1 %,
2 – 37,8 %,
7 – 57,2 %,
1 – 33,9 %,
6 – 53,3 %,
0...9
0 – 30,0 %
5 – 49,4 %,
4 – 86,1 %,
9 – 100 %,
3 – 83,3 %,
8 – 97,2 %,
2 – 80,6 %,
7 – 94,4 %,
1 – 77,8 %,
6 – 91,7 %,
0...9
0 – 75,0 %
5 – 88,9 %,
Data
0, 30—100
0—9
30—65
75—100
0—1
0—1
3—9
0—1
0—2
Si no se realiza ninguna
acción durante 10 s,
los cambios no se efec-
tuarán
Para salir del menú de
configuración y mostrar
el escalón – posición
actual
Values
0 =
0 % Us* (0 VAC)
30 =
30 % Us (70 VAC)
100 =
100 % Us (230 VAC)
0 =
...
9 =
30 =
30 % Us (70 VAC)
65 =
65 % Us (150 VAC)
75 =
75 % (170 VAC )
100 =
100 % (230 VAC)
0 =
1 =
0 =
1 =
5 =
0 =
1 =
0 =
Off (a decimal point is visible)
1 =
On (the current step is visible)
2 =
Modbus connected ('d' is visible)
step 0
...
step 9
Normal
Inverse
Kick start
Soft start
5 s
Off
On
9 - 11