Installation and connection (continued)
5.2

Electrical Connection

The electrical connection is made via a plug connection
(for pin assignment see Tab. 5-2).
See the information about Shielding and cable
routing on page 9.
2
5
1
3
4
Fig. 5-3:
Pin assignment of S92 (view from above on BTL)
Pin ...-B15AA... ...-B15A1... ...-B15AE... ...-B15A5...
1
10...30 V
2
0...10 V
10...0 V
3
4
Unassigned
5
Reference potential for supply voltage and EMC-GND.
1)
2)
Unassigned leads that are not used can be connected to the GND on
the controller side but not to the shield.
Tab. 5-2:
Pin assignment S92
www.balluff.com
4...20 mA
20...4 mA
GND
1)
2)
0 V
5.3

Shielding and cable routing

Defined ground!
The BTL and the control cabinet must be at the
same ground potential.
Shielding
Observe the following instructions to ensure
electromagnetic compatibility (EMC):
Connect BTL and controller using a shielded cable.
Shielding: Braided copper shield with minimum 85%
coverage.
Shield is internally connected to connector housing.
Magnetic fields
The position measuring system is a magnetostrictive
system. Ensure that there is sufficient distance between
the BTL and the transducer/holding cylinder and strong,
external magnetic fields.
Cable routing
Do not route the cable between the BTL, controller, and
power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Cable length
BTL ...-B15AA/A1...
BTL ...-B15AE/A5...
1)
Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields.
Tab. 5-3:
BTL cable lengths
Max. 30 m
1)
Max. 100 m
1)