Installing the Zoneline
8. Connect Auxiliary Features, if required
Auxiliary Controls - Terminal Connections
NOTE: Connector Kit RAKCDC is required to make CDC
electrical connections.
(See wiring diagrams for RAKCDC below.)
The auxiliary control terminal connects are located on the
front of the unit.
1. To connect auxiliary devices to the unit, connect the
wires from the RAKCDC Kit to the wires from the
auxiliary devices. Then insert the RAKCDC connector
into the mating control board connector next to the
thermostat connector.
2. After all desired connections have been made, replace
the front case panel.
The owner is responsible for making all connections and setting the appropriate AUX SET mode.
NOTICE: Improper wiring may damage the Zoneline electronics. No common busing is permitted. Damage or
erratic operation may result. A separate wire pair must be run from each separate controlling switch to each
individual Zoneline.
Central Desk Control (Field Supplied)
The Central Desk Control is a feature that allows the unit to be made operable/inoperable from a remote location.
Operation of the feature requires that an ON-OFF switch at the remote location be wired to the two CDC terminals
on the control panel of the Zoneline. When the remote switch is CLOSED, the unit cannot be operated in the Fan,
Cool, or Heat modes by the control. The Freeze Sentinel
and the Heat Sentinel features remain operable. When
the remote switch is Open, the unit is fully operable by
control.
The RAKCDC accessory must be used with a central
desk control system. No "Common Busing" is permitted.
NOTICE: Improper CDC wiring may damage the
Zoneline electronics or cause erratic Zoneline operation.
No common busing is permitted. A separate wire pair
must be run from each separate controlling switch to
each individual Zoneline.
Use only Class 2 wiring.