Output charts water S10-W
Type
Fan
Airflow
position
[m
S10-100W
Max
1300
Min
900
S10-150W
Max
2100
Min
1250
S10-200W
Max
2600
Min
1800
Type
Fan
Airflow
position
[m
S10-100W
Max
1300
Min
900
S10-150W
Max
2100
Min
1250
S10-200W
Max
2600
Min
1800
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +32 °C
Output
Return
water
temp.
/h]
[kW]
[°C]
3
6,4
50,0
4,5
45,0
10,5
45,0
6,6
40,0
13,1
45,0
9,1
40,0
Supply water temperature: 55°C
Room temperature: +18 °C
Outlet air temperature: +29 °C
Output
Return
water
temp.
/h]
[kW]
[°C]
3
6,4
50,0
4,2
44,0
10,3
46,0
6,1
39,0
12,7
46,0
8,5
39,0
S10-W
Water temperature: 60/40 °C
Room temperature: +18 °C
Water
Pressure
Output *
flow
drop
[l/s]
[kPa]
[kW]
0,16
7,1
4,7
0,07
1,8
3,7
0,17
11,3
9,2
0,08
3,0
6,6
0,21
20,3
11,5
0,11
6,5
9,1
Water temperature: 55/35°C
Room temperature: +18 °C
Water
Pressure
Output *
flow
drop
[l/s]
[kPa]
[kW]
0,34
29,3
3,5
0,09
2,7
2,6
0,28
27,5
7,3
0,09
4,1
5,2
0,34
48,7
9,3
0,13
8,8
7,4
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
28,6
0,06
1,2
30,0
0,05
0,8
30,8
0,11
5,4
33,5
0,08
3,0
31,0
0,14
9,8
32,9
0,11
6,5
Outlet
Water
Pressure
2
air temp.
flow
drop
[°C]
[l/s]
[kPa]
25,9
0,04
0,7
26,6
0,03
0,5
28,2
0,09
3,7
30,3
0,06
2,1
28,5
0,11
6,9
30,0
0,09
4,6
19