3.4
Electrical connection
Important :
personnel. Check that the cable supplying the technical room has a sufficiently large cross-section
to support the additional consumption required by the machine.
The heat pump must be supplied from an independent D-curve circuit breaker which can be either on
the main electrical panel equipped with a differential or on an independent panel connected to the main panel,
which will have a differential. If this is not the case, add a differential to the independent panel of your heat pump.
Référence
DC 35
DC 55
DC 75
DC 95
DC 115
Electrical connection on the terminal block of the heat pump
Monophase
Unscrew the handle to access the electrical connection
The connection of your heat pump must be carried out by authorised and qualified
D-Curve circuit
Power Supply
breaker power
Monophasé 230 V
Monophasé 230 V
Monophasé 230 V
Monophasé 230 V
Monophasé 230 V
Cable section according to the distance
between the circuit breaker and the heat pump
- 10 m
16 Ampères
3G2.5 mm2
16 Ampères
3G2.5 mm2
20 Ampères
3G2.5 mm2
25 Ampères
3G2.5 mm2
25 Ampères
3G2.5 mm2
10 -15 m
+ 15 m
3G2.5 mm2
3G6 mm2
3G2.5 mm2
3G6 mm2
3G2.5 mm2
3G6 mm2
3G2.5 mm2
3G6 mm2
3G2.5 mm2
3G6 mm2
Three-phase
L :
Line
N :
Neutral
:
Earth
44