5.9 List of parameters and error codes
Error / Failure
Water inlet temperature sensor
fault
Water outlet temperature sensor
fault
Ambient temperature sensor fault
Heat exchanger temperature
sensor fault 1
Défaut sonde de température
échangeur 2
Temperature sensor fault SUT
ET temperature probe fault
ET probe fault (protection)
Antifreeze temperature probe
fault
Pressure sensor fault
Compressor high pressure
Compressor low pressure
Water flow switch
Low temperature protection
Water inlet and outlet gap
Code Motive
P01
The probe is damaged or
short-circuited
P02
The probe is damaged or
short-circuited
P04
The probe is damaged or
short-circuited
P05
The probe is damaged or
short-circuited
P15
The probe is damaged or
short-circuited
P07
The probe is damaged or
short-circuited
P081
The probe is damaged or
short-circuited
P 082
Compressor overload
P 09
The probe is damaged or
short-circuited
PP
The probe is damaged or
short-circuited
E 01
Compressor pressure problem
detected
E 02
Problem detected at
compressor pressure
E 03
Flow sensor error detected
E 05
Ambient or water temperature
is too low
E 06
The water flow is not sufficient
Method of resolution
Check or change the probe
Check or change the probe
Check or change the probe
Check or change the probe
Check or change the probe
Check or change the probe
Check or change the probe
Check if the system and the
compressor are working
properly
Check or change the probe
Check or change the probe
Check the valve settings (
By Pass open 70% - Water
inlet valve open 100% and
water outlet valve open
70% ). Check the pressure
sensor and the flow sensor.
Check and/or replace the
pressure sensor and
contact your installer to
check the refrigerant
circuit.
Check the water circulation
in your hydraulic circuit if
the filtration pump is not
turned on your heat pump
will not work. Check the
valve settings ( By Pass
open 70% - Water inlet
valve open 100% and water
outlet valve open 70% ).
Check and / or replace the
flow sensor
Check the water and
ambient temperatures
Check the water circulation
and the valve settings ( By
Pass open 70% - Water
inlet valve open 100% and
58