Arrancador suave serie NJR2-D
Nota: Ie, significa corriente nominal del motor, que es consistente con el valor F19.
C.1 Diagrama de cableado básico de Mando-uno-uno
L1
L2
Q F
R
S
U 1
V1
W 1
KM 1
U
V
M
Apéndice C Atlas de aplicaciones
L3
SB1( sof t st ar t )
FU
KH
T
K1
W
1
2
But t on box besi de t he m achi ne
A1
A2
A
A
TA
D escr i pt i on:
1、As the max output capacity of bypass relay K1 is 5A
only,it is unable to control high-power AC contactor
directly,for AC contactors of 167A above,intermediate
relay is recommended;
2、When wiring in this way,it starts when KA1 closes,
stops when KA1 opens;
3、Three-wire control mode can be used,which could leave
out the KA1 intermediate relay ;
4、KH thermal relay can be omitted(soft starter itself
already has overload protection function);
5、Terminal number accords with the description of control
terminals.
R Q
K3
SB2( sof t st op)
KA1
R Q
K1
R Q
K3
K2
3
4
5
6
68
N
R D
Faul t i ndi cat i on
R un/ St op cont r ol
KA1
Bypass cont act or
KM 1
Bypass i ndi cat i on
H D
X3
C O M
R U N
KA1
SB3
I nst ant aneous st op
STO P